0.6/1kv VV YJV Single Core XLPE PVC Insulated Flexible 10mm 16mm 20mm 25mm Power Cable
168 Cable is one of the leading factory for the wire and cable production in China, our mainly products are bare strand conductors, such as AAC, ACSR, AAAC, ACAR, aluminum clad steel conductor; 0.6/1KV aerial bundled cable (ABC Cable), Plastic insulated wire, XLPE power cable, home wire, armored cables, Plastic insulated control cables, low smoke halogen-free cable, overhead insulated cable, fire resistant cable, PVC insulated wires and cables, computer cable , frequency conversion cable, aluminum alloy cable, minerals insulated fireproof cables etc. At the same time provides OEM for various special type cable according to customers' demand.
1. Standard
According to GB12706( Equal to IEC60502) Also we can do according to the standard of ASTM, BS, DIN, VDE, JIS, AEIC and AS/NZS or other standards that you need.
2. Applications:
PVC insulated power cable is suitable for laying fixed in power transmission and distribution lines with A.C. 50HZ and rated voltage of 0.6/1kV.
Cross-linked polyethylene(XLPE) insulated power cables is characterized with high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level.
This product is suitable and designed for power transmission and distribution system of rated voltage 0.6/1kv. In terms of the main feature of anti-flaming cable,the cable is not easy to burn or continued burning, so it is widely used in the power station, subway, tunnel, high building, large industrial and mining enterprise, oil field, and other places.
3.Product Characteristics:
1). Max temperature for Long-time working:≤90°C
2). Installing temperature: ≥0°C
3). Max short-circuit (Not more than5 Sec) temperature: 250°C
4). The cable can’t be laid without the limit of fall with enough mechanical pull and the single core cable can’t be laid in iron tube or fixed by circled iron tools around cables.
5). Rated Voltage: 0.6/1KV, 3.6/6KV, 6/10KV, 8.7/15kv, 12/15kv, 12/20kv, 18/20kv, 18/30kv, 21/35kv, 26/35kv, 36/63kv, 48/63kv, 64/110kv, 127/220kv
6). Conductor: copper or aluminum
7). Sectional area: 25 - 630mm2
8). Insulation: XLPE, PVC
9). No. of cores: 1, 2, 3, 4, 5
10). Armor: steel wire, steel tape, non-magnetic material
11). Over sheath: PVC, PE
TYPE | NAME | Main Application | |
CU core | AL core | ||
VV | VLV | PVC insulated, PVC sheathed power cable | For laying indoor, tunnel, pipe and underground. Can't bear the external mechanical force, but can bear the traction during laying |
YJV/YJY | YJLV/YJLY | XLPE insulated, PVC/PE sheathed power cable | |
YJV22/YJV23 | YJLV22/YJLV23 | XLPE insulated, steel tape armored, PVC/PE sheathed power cable | For laying indoor, tunnel, pipe and underground. Can bear external mechanical force, but can’t bear large pulling force. |
YJV32/YJV33 | YJLV32/YJLV33 | XLPE insulated, thin round steel wire armored, PVC/PE sheathed power cable | For laying in tunnel, pipe, water, underground and shaft with large difference of level. Can bear external mechanical forces and moderate pulling force. |
YJV42/YJV43 | YJLV42/YJLV43 | XLPE insulated, thick round steel wire armored, PVC/PE sheathed power cable | For laying in water and seabed. Can bear positive pressure and pulling force. |
Note:"ZR-"Include ABC three kinds of flame retardant cables,which are special indicated in "ZRA-" or "ZRB-" "ZRC-".For example:"ZRB-YJV","ZRA-YJV22".
4. Main Technical Indexes
1):The detail technical data voltage armoured power cable as below for reference,any customized is available.
U0/Um(KV) | 1st class | 0.6/1 | 1.8/3 | 3.6/6 | 6/10 | 8.7/15 | 12/20 | 18/30 | 21/35 |
No. Of Core | 2nd class | 1/1 | 3/3 | 6/6 | 8.7/10 | 12/15 | 18/20 | 18/20 | 26/35 |
1 Core | Section area(mm2) | 1.5-800 | 25-800 | 25-1200 | 25-1200 | 35-1200 | 50-1200 | 50-1200 | 50-1200 |
2 Core | Section area(mm2) | 1.5-185 | 25-185 | / | / | / | / | / | / |
3 Core | Section area(mm2) | 1.5-400 | 25-400 | 25-400 | 25-400 | 35-400 | 50-400 | 50-400 | 50-400 |
4 Core | Section area(mm2) | 2.5-400 | 25-400 | / | / | / | / | / | / |
5 Core | Section area(mm2) | 2.5-400 | 25-400 | / | / | / | / | / | / |
2): DC resistance: conductor resistance of finished cable at 20ºC per kilometer is not more than the following values.
Nominal section area (mm2) | Copper core | Aluminum core | Nominal section area (mm2) | Copper core | Aluminum core |
1.5 | 12.1 | 18.1 | 95 | 0.193 | 0.32 |
2.5 | 7.41 | 12.1 | 120 | 0.153 | 0.253 |
4 | 4.61 | 7.41 | 150 | 0.124 | 0.206 |
6 | 3.08 | 4.61 | 185 | 0.099 | 0.164 |
10 | 1.83 | 3.08 | 240 | 0.0754 | 0.125 |
16 | 1.15 | 1.91 | 300 | 0.0601 | 0.1 |
25 | 0.727 | 1.2 | 400 | 0.047 | 0.778 |
35 | 0.524 | 0.868 | 500 | 0.0366 | 0.0605 |
50 | 0.387 | 0.641 | 630 | 0.0283 | 0.0469 |
70 | 0.268 | 0.443 | 800 | 0.0221 | 0.0367 |
3): Voltage Test and Partial Discharge Test
Rate | 0.6/1 | 1.8/3 | 3.6/6 | 6/6 6/10 | 8.7/10 8.7/15 | 12/20 | 18/20 18/30 | 21/35 | 26/35 | |
Item | ||||||||||
Voltage | Test Voltage | 3.5 | 6.5 | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
Test Time | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
Partial Discharge Test | Test Voltage | - | - | 6.2 | 10.4 | 15.1 | 20.8 | 31.1 | 36.3 | 45 |
Discharge Capacity | - | - | 10 | 10 | 10 | 10 | 10 | 10 | 10 |