Characteristics LC1D40AM7
Main
Range of product TeSys D
Product or component type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-1
AC-3
Poles description 3P
Power pole contact composition 3 NO
[Ue] rated operational voltage <= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit
[Ie] rated operational current 60 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
40 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
Motor power kW 30 kW at 660...690 V AC 50/60 Hz
22 kW at 500 V AC 50/60 Hz
22 kW at 415...440 V AC 50/60 Hz
18.5 kW at 380...400 V AC 50/60 Hz
11 kW at 220...230 V AC 50/60 Hz
Motor power HP (UL / CSA) 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 115 V AC 50/60 Hz for 1 phase motors
30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
Control circuit type AC 50/60 Hz
Control circuit voltage 220 V AC 50/60 Hz
Auxiliary contact composition 1 NO + 1 NC
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Overvoltage category III
[Ith] conventional free air thermal current 60 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
250 A DC for signalling circuit conforming to IEC 60947-5-1
140 A AC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 165 A <= 40 °C 1 min power circuit
72 A <= 40 °C 10 min power circuit
720 A <= 40 °C 1 s power circuit
320 A <= 40 °C 10 s power circuit
140 A 100 ms signalling circuit
120 A 500 ms signalling circuit
100 A 1 s signalling circuit
Associated fuse rating 80 A gG at <= 690 V coordination type 2 for power circuit
80 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
Average impedance 1.50 mOhm at 50 Hz - Ith 60 A for power circuit
[Ui] rated insulation voltage 600 V for signalling circuit certifications UL
600 V for signalling circuit certifications CSA
690 V for signalling circuit conforming to IEC 60947-1
600 V for power circuit certifications UL
600 V for power circuit certifications CSA
690 V for power circuit conforming to IEC 60947-4-1
Electrical durability 1.5 Mcycles 40 A AC-3 at Ue <= 440 V
1.4 Mcycles 60 A AC-1 at Ue <= 440 V
Power dissipation per pole 5.4 W AC-1
2.4 W AC-3
Safety cover With
Mounting support Plate
Rail
Standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 No 14
Product certifications CCC
CSA
GOST
UL
Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: solid - without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: solid - without cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: flexible - with cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: flexible - with cable end
Power circuit: EverLink BTR screw connectors 2 cable(s) 1...25 mm² - cable stiffness: flexible - without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1...35 mm² - cable stiffness: flexible - without cable end
Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25...35 mm² hexagonal 4 mm
Power circuit: 5 N.m - on EverLink BTR screw connectors - cable <= 25 mm² hexagonal 4 mm
Operating time 12...26 ms closing
4...19 ms opening
Safety reliability level B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Mechanical durability 6 Mcycles
Operating rate 3600 cyc/h at <= 60 °C

 Schneider LC-D Contactors (3)-14Schneider LC-D Contactors (3)-24

0.0226 s.