Сохранить в закладки:
Item name | On-line Pure Sine UPS 1000W | ||
Model | YBUPS-1000 | ||
Inverter output | Rate Power(Typ.) | 1000W Peak 2000W | |
AC power | 220V | ||
Frequency | 50HZ±0.5HZ | ||
Sine wave | Pure sine wave(THD<3%) | ||
Inverter Input | Battery Voltage | 12V | |
Voltage range(Typ.) | 10V-15.8V | ||
Input DC current(Typ.) | 90A | ||
Empty load consume current | ≤0.3A | ||
shut down mode current | ≤20mA | ||
Max efficient(Typ.) | ≥88% | ||
Battery type | Lifepo4 batteries | ||
Battery input protect | Fuse | 35A*4 | |
Low voltage alarm | 10.5V±0.5V | ||
Low voltage shut down | 9.5V±0.5V | ||
High voltage protect | 15.5V±0.5V | ||
Reverse protect | Internal fuse | ||
Inverter output protect | 75℃±5℃ | ||
Red light one with alarm ,cut off output | |||
Output short circuit | Rad light flash, recover output after reduce loads | ||
≥ 1100W | |||
Red light on ,self lock,recover normal output after short circuit canceled | |||
Charging input | Rate power | 220V | |
Frequency | 50/60HZ±0.5HZ | ||
Full load efficiency | ≥80% | ||
Charging output method | The output voltage three-stage charging | Stable current charging current 10A charging light is on | |
Stable charging voltage 14.4V charging light is on | |||
Float charging voltage 15.0V charging light is on | |||
Charger input protect | Fuse | 5A*1 | |
Overload | 5A overload protect | ||
Homeppower over voltage/thunder attack | Varistor | ||
Charging output protect | Short circuit protect | yes | |
Reverse protect | Internal fuse | ||
Switch | City power to inverter time | ≤20mS | |
Inverter to city power time | ≤20mS | ||
USB | Output voltage | 5V | |
Output current | 2A | ||
Environment | Working temperature | 0-40℃ | |
Working humidity | 10-90%RH, | ||
Storage temp,humidity | 20℃~60℃ 5-95%RH | ||
Solar Input | Solar Input type | Solar Socket | |
Input Max | DC 10A 18V | ||
Remark | Unless otherwise specified, all specifications are measured at 25 ° C ambient temperature. | ||
Size | 430*144*223mm |