Сохранить в закладки:
input signal | Thermal resistance(RTD): Pt100,Pt1000,Cu50 | ||||||
Thermocouple(TC):K,S,R,B,N,E,J,T | |||||||
Temperature range | -270~+1820℃(set according to sensor measurement capability) | ||||||
Conversion accuracy | ≤0.2% or 0.2K | ||||||
Output signal | 4-20 mA(two-wire),HART | ||||||
Alarm | When the sensor fails (open circuit or short circuit), the output drops to ≤3.6mA or the output rises to ≥21.5mA | ||||||
Maximum load (Note 1) | (V power- 9 V)/0.025A (output current) | ||||||
Limit current | ≤25mA | ||||||
Power supply voltage (Note 2) | 9...30VDC | ||||||
Response time | 1S | ||||||
Lightning protection (Note 3) | ±4000V(≤5 times) | ||||||
Anti-pulse group(Note 4) | ±4000V | ||||||
Anti-radio frequency interference | >10V/m(80MHz~1000MHz) | ||||||
Ambient temperature | -40~85℃ | ||||||
Temperature drift | 0.008%FS/1℃ | ||||||
Long-term stability | ≤0.1℃/year or 0.05%/year |
Model | Code | Note | ||||
GTM | Smart temperature transmitter | |||||
Input signal(note 1) | A | Pt100 | ||||
RT | Pt1000 | |||||
RC | Cu50 | |||||
K | K-type thermocouple | |||||
S | S-type thermocouple | |||||
R | R-type thermocouple | |||||
B | B-type thermocouple | |||||
N | N-type thermocouple | |||||
E | E-type thermocouple | |||||
J | J-type thermocouple | |||||
T | T-type thermocouple | |||||
Output signal | A | 4-20 mA(two-wire) | ||||
H(note 2) | HART(two-wire 4-20mA) | |||||
Configuration method | A | Slide switch | ||||
P | Slide switch+PC programming | |||||
Range | A(note 3) | Factory default settings | ||||
X | User specified code (limited to 15 ranges) | |||||
Installation | A | Top installation (screw fixation) | ||||
D | Rail installation (35mm DIN rail) | |||||
Annex | A | Standard | ||||
B | With calibration report |