Product Description

Asenware conventional fire alarm control panel for fire alarm system 4 zone

Features: each zone fire relay output.  optional GSM module for fire alarm by SMS .


1 AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2 It is modularized design, the panel can expend from 1 zone to 32 zones easily.
3 It has 2 level control mode by a lock
4 It has 24VDC and 5VDC power supply output.
5 It has FIRE and FAULT signal output.
6 It has 2 general sounders output.
7 Each zone has 1 circuit detectors input .
8 Each zone can be disable by a button.
9 It has RESET button to reset the panel.
10 It has SILENCE button to stop BUZZER and SOUNDERS.
11 It has EVACUATE button to start a manual fire alarm immediately.
12 It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.

Parameter
\t
ITEM
\t
1 Zone panel
\t
2 Zone panel
\t
4-8 Zone panel
\t
4-32 Zone panel
\t
Model No.
\t
AW-CFP2166-1
\t
AW-CFP2166-2
\t
AW-CFP2166- 4-8
\t
AW-CFP2166- 4-32
\t
Power specification
\t
\t
Mains supply voltage
\t
110VAC or 240VAC
\t
Internal power supply
\t
27.2VDC
\t
Total output current limited
\t
500mA @240VAC
\t
500mA @240VAC
\t
3A @ 240VAC
\t
3A @ 240VAC
\t
Batteries (default configuration)
\t
12V2AH*2
\t
\t
\t
\t
Detector circuit specification
\t
\t
\t
\t
\t
Number of circuit
\t
1
\t
2
\t
4-8
\t
4-32
\t
Line fault monitor for detector removal
\t
Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
\t
End of Line device
\t
6.8k Ω,5% tolerance, 0.25W (color code-blue, grey, red, gold)
\t
Detector continuity diodes
\t
Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
\t
Call point resistor value
\t
470 to 680 Ω, 0.225 or 0.5 watt
\t
Maximum number of smoke/heat detectors per zone
\t
20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maximum voltage drop must not exceed 12 volts.
\t
Sounder circuit specification
\t
\t
Number of general circuits
\t
2
\t
End of line resistor value
\t
6.8k Ω,5% tolerance, 0.25W (color code-blue, grey, red, gold)
\t
Fire and fault output
\t
\t
Output type
\t
Dry relay output :NC and NO relay; wet source output
\t
Maximum current
\t
100mA
\t
Dimensions(mm)
\t
272*200*70mm
\t
320*231*90mm
\t
395X502X124
\t
362X565X124
Detailed Images
Products

Our product series:
1. 2100 series: addressable fire alarm and control system for big project, minimum addresses are 648,648*2,648*n.
2. 2188 series: addressable fire alarm system for small project, 100/200/324 addresses.
3. 2166 series: conventional fire alarm system, we have 1-32 zone panel.
4. 2159 series: automatic fire extinguishing controller. 

5. Led emergency lights, twin spot emergency light and exit sign.

6. Kitchen fire suppression system.

Packing & Delivery

By Express, EMS,DHL,FedEx,UPS etc, by air, by sea.

Our Company

Asenware Test and Control Technology Co., Ltd

Asenware Test and Control Technology Co., Ltd, founded in 2005, is distinguished by the experience and expertise of more than 11 years as one of the largest manufacturers and suppliers of China’s fire and security alarm products. Asenware is also a trusted brand of fire system solutions for all customers from all over the world.