Share on (10000008329266):

Online UPS for IDEAL Choice 9300LB LV Online UPS single-phase 1KVA
Tower 1KVA Series Online UPS single-phase 1KVA
IDEAL-9301LB UPS Series is true sine wave double conversion Online UPS tower type model that provides output power factor 0.8 for high performance and efficiency. With Microprocessor control design, it lowers the defective rate of UPS to guarantee high reliability and to protect any critical applications. Online UPS single-phase 1KVA
* Intelligent Slot (SNMP) and USB management software to monitor UPS status Tower Online UPS 1000VA
* ECO mode High efficiency mode for power saving Tower Online UPS 1000VA
* Wide input range for extreme voltage instability Tower Online UPS 1000VA
* Advanced microprocessor control technology online UPS
* External battery bank to extend back-up time Tower Online UPS 1000VA
* True double conversion On Line UPS Tower Online UPS 1000VA
* Emergency power-off EPO function Power supply Online UPS 1000VA
* Automatic self-testing function Power supply Online UPS 1000VA

Applied to replace bulky transformers, relays and mechanical bypass switch with smaller, more intelligent functional equivalents. Power supply Online UPS 1000VA
UPS system works by converting power from AC to DC and then back to AC. Supplying power with zero transfer time to the battery to ensure uninterrupted back-up power when AC power is abnormal, make it ideal for any sensitive devices.
Supporting Wide Input Voltage range can offer stable power supplying even in bad AC environment.
External battery bank can provide continuous backup power during long-term outage.
Intelligent self-testing function can inspect battery and UPS status to avoid causing any negligence or loss. online UPS
Offering well and full range protection for computer center, accounting center, office and home applications. For Online UPS 1KVA model(800W), 3sets PC can be connected in the same time. Power supply Online UPS 1000VA
MODEL | IDEAL-9301LB | IDEAL-9301LBE | ||||
CAPACITY UPS | 1KVA/0.8KW | |||||
INPUT | ||||||
Voltage | 1 Phase 2 Wires + Ground 100/110/150/120Vac | |||||
Voltage Range | 100/110/150/120Vac: 55 - 150Vac | |||||
Frequency | 50Hz or 60Hz (Auto Sensing) | |||||
THDi | < 5% at full Load | |||||
OUTPUT | ||||||
Voltage | 100/110/150/120Vac | |||||
Voltage Regulation | 100/110/150/120Vac:< 1% | |||||
Frequency (Battery Mode) | 100/110/150/120Vac: 50Hz or 60Hz +/- 0.1Hz | |||||
Waveform | Pure Sinewave | |||||
THD | 100/110/150/120Vac: < 4% (Linear Load), < 8% (Non-linear Load) | |||||
Crest Ratio | 3:1 | |||||
EFFICIENCY | ||||||
To AC Mode | 100/110/115/120Vac: > 89% at Full Load and Battery Full Charged | |||||
To Battery Mode | 100/110/115/120Vac: > 85% at Full Load and Battery Full Charged | |||||
To ECO Mode | 100/110/115/120Vac: > 95% at Full Load and Battery Full Charged | |||||
BATTERY | ||||||
Voltage | 36VDC | |||||
Type | 12V/7AH*3pcs | Extendable | ||||
Recharge Time | 5Hrs to 90% | Depend on Capacity of External Battery | ||||
TRANSFER TIME | ||||||
Line Mode to Battery Mode | 0ms | |||||
Inverter to Bypass, ECO Mode | < 4ms | |||||
ECO Mode to Inverter | < 10ms | |||||
DISPLAY | ||||||
LCD Display | Input, Output, Load, Battery, Mode/Fault/Warning code, Inverter operating, Bypass operating, Output voltage and frequency and Bypass disable / enable selection information | |||||
COMMUNICATIONS | ||||||
Interface (Port) | USB Port | |||||
Intelligent Slot | Slot for SNMP or AS400 card (Optional) | |||||
EPO | Emergency Power Off | |||||
ENVIRONMENT | ||||||
Temperature | 0 - 40°C | |||||
Humidity | 20-90%, non-condensing | |||||
Acoustic Noise | 100/110/115/120VAC: < 45dB at 1M | |||||
PHYSICAL | ||||||
Dimension(D*W*H) | 420*145*230mm | |||||

IDEAL POWER CO., LTD was founded in 1996 and committed to design and manufacture reliable and qualified full range of power products, including Uninterruptible Power Supply (UPS), Inverter, Automatic Voltage Regulator (AVR), Voltage Protector (VP) and Surge Protector (SP).
With more than 20 years' experience of OEM/ODM in power products, IDEAL POWER strives to achieve the mission to provide products with high quality and better performance to meet customers' demand in the world.

We, IDEAL, are dedicating on product development and training professional team, we focus on the global market trend to provide innovative power for customers. IDEAL engineering team has professional background experience and technical knowledge and skill, devoting to integrate global market tendency with new technology to ensure products meet the global customer demand. IDEAL design team help customer design customized product package to establish admirable corporate image for marketing.
We are convinced that establishing long-term relationship of mutual trust and mutual benefit between IDEAL and customers is the motion for us to thrive.
With well-trained and professional team, IDEAL support best service and qualified products to customers globally.


1) ODM/OEM experience for more than 20 years.
2) Well-organized manufacturing bases to meet worldwide growing demand.
3) Customized products to meet various applications.
4) Full range of power products
5) High quality products supported by strict quality control system
6) Well-trained workforce and engineer team.
7) Reliable manufacturing supplier on E-commerce online platform

Q1: Why you should install UPS?
When AC Power is off, UPS will offer emergency back-up power to your electronic devices for data loss protection. Power surges are a threat everywhere. UPS can provide fully power protection for over-voltage, under-voltage and surge to offer smooth and consistent flow of power quality to your appliances.
Q2: What electronic appliances should be protected?
All electronic appliances that need long programming times or have to be always accessible would be better to install with a UPS system. This includes computer, medical equipment, data center, server room, networking system and any important electronic appliances.
However, it is not recommended to connect UPS with laser printer or office multifunction fax/printer because they will draw a high initial inrush current at start-up. A typical UPS cannot deal with such a spike.
Q3: What factors can affect UPS battery life time?
Batteries must be kept at ambient temperature of 25°C (77°F). If battery is operated at higher temperatures, its average life will be shortened. The number and length of battery discharges affect a battery's efficiency to deliver power. The more or deeper discharges, the shorter the battery's life will be.
If a battery is undersized for a load, battery run time and life expectancy will also be shortened.
Therefore, it is recommended to replace the batteries every 3 years after initiating the unit.
Recharge batteries every 3 months is necessary if it is not in use.
New products from manufacturers at wholesale prices