Share on:
Specification
Index | MXD33 100KVA | |
Input Mains | ||
Related Voltage(V) | 380Vac three - phase + N | |
Related Voltage & Range(V) | 380V ± 25% | |
Frequency & Range(V) | 50 / 60Hz ± 4Hz | |
Bypass Input | ||
Related Voltage(V) | 380V ( Line Voltage ) | |
Related Voltage & Range(V) | 380V ± 25% | |
Frequency & Range(Hz) | 50 / 60Hz ± 4Hz | |
Output | ||
Related Power | 100K/80KW | |
Related Voltage(V) | 380V ( Line Voltage ) | |
Related Voltage & Stability | 380V ± 2% | |
THD i | Linear Load | ≤3% |
Non-linear Load | ≤8% | |
Output Power factor | 0.8 (Lag) | |
Tracking Fruquency & Range(Hz) | 50 / 60Hz ± 4Hz | |
Fruquency & Stability (Battery Inverter) | (50 / 60+0.1) Hz | |
Overload Capaility |
1.Less than 105% for overload alarm; 105% ± 5%-125% ± 5%,for 2 minutes; 2.125% ± 5%-150% ± 5% for 30 Second; 3.More than150% ± 5% for 0.5 second;
| |
Converting time (Normal Mode) | <1mS | |
System Efficiency (ECO Mode) | <10mS | |
System | ||
Display | ≥90 | |
EMS/EMI | Transmission | ≥ 96% |
Radiation | LCD / LED | |
Resisting Interfererce | IEC 61000-4-2.4.5 Level, IEC61000-4-3 lEVEL III | |
Safety Requirements | GB4943-2001 / IEC62040-1 | |
Noise Level (1M) | ≤70dB | |
Isolate Impedance | >2M (500VDC) | |
Surge Current Protection | IEC60664-1 IV | |
Environ-ment | ||
Operating Temperatures | 0℃~40℃ | |
Elevation | <1000m | |
Storing Temperatures | (-15℃~45℃) | |
Operation Humidity | 20%~95% | |
Battery | ||
Battery | 384VDC |