High quality CE 10ton 35kw heating ang cooling rooftop air conditioner for buliding Cinema

Share on (1600308335992):


Price:RUB 359,597.94

Quantity:


Product Overview

Description

4

Product form:
Single cold type;Heat pump type;Fresh air type;Partial fresh air type;Heat recovery type;All return types;Constant temperature and humidity;Parameters on this page are all return types

Different types of units can be added to achieve different functions, the specific situation, please consult customer service

For other types of DX units, please click the link to enter

Product features:
1. With fully closed screw compressor, there are few moving parts in the unit and the reliability
is high.
2. Parallel connection of two presses increases component load by 15-30%.
3 Microcomputer automatic control, LED display, convenient operation, complete functions.
4 Integrated unit design, flexible and convenient installation, can be directly installed in the roof or courtyard, without special computer room, save space.
5. Various ways of air supply: side return side air supply, down return down air supply, up 

return up air supply and direct air supply.
6. Unit operating range from 10 degrees below zero to 50 degrees above zero

 

Nming Rules:
Product Naming Rules
W  R  F  1  9  0
1   2   3  4  5  6
NO.1 W=rooftop air conditioner
NO.2 R=heat pump;single cooling doesn't indicate
NO.3 F=winding cooling
NO.4,5,6:refrigerating capacity when No 4,5 is 0,it doesn't indicate

Product Parameters

Product parameters

rooftop packaged unit 2

 

Model WRF 72 90 105 120 140 150 180 210 300 400
Refrigeration Capacity kW 70 90 105 120 140 149 180 210 298 392
Heating Capacity kW 75.4 96.2 113.2 128.3 150 159.2 192.5 226 318 414
Power Supply 380V-420V/3Ph/50Hz
Refrigeration Input Power kW 26.7 32.9 39.7 45.1 55.7 55.1 69.9 83 106.7 140.2
Heating Input Power kW 24.8 30.4 36.7 41.7 51.8 51.5 64.8 77 100 133.8
Cryogen R410a/R22/R407c
Compressor  Type Hermetic Scroll Compressor
Number 2 3 3 4 4 2 6 6 4 5
Condenser Type Aluminum Fin With Copper Tube Sleeve
Fan Number 1 2 4 6
Type Direct Drive
 Power kW 2.2 2.2 3 3 4.4 4.4 4.4 6 8.8 11
Volume m3 /h 27000 33000 42000 42000 54000 54000 66000 84000 108000 135000
evaporator Type Aluminum Fin With Copper Tube Sleeve
Fan Number 1
Power kW 4 5.5 5.5 7.5 11 11 15 15 18.5 30
Volume m3 /h 12500 16000 19500 21000 25000 26000 32000 38000 54000 67000
Type Pulley(Customized EC Fan,Fan Can Be Frequency Conversion)
Pressure Of Wind Outside The Machine(Pa) 300 400 500
Filter Aluminum filter G3(Different Filters Can Be Added According To Requirements)
Refrigerant Charge(kg) 2x8.5 3x7.5 3x8.5 4x7.5 4x8.5 2x17 6x7.5 6x8.5 4x14 5x14.2
Dimensions Length mm 2298 2878 2878 3626 3626 3626 4690 4690 5660 7300
Width mm 1650 2140 2270 2200 2200 2200 2330 2330 2330 2330
Height mm 1400 1964 1964 2047 2047 2047 2055 2055 2055 2055
Weight kg 860 1160 1350 1710 1820 1850 2180 2430 2860 3500
Unit Cooling Capacity And Power Consumption Test Conditions:Environment Temperature Dry / Wet 35/24℃,Indoor Temperature Dry / Wet 27/19℃
Unit Heating Capacity And Power Consumption Test Conditions:Environment Temperature Dry / Wet 7/6℃,Indoor Temperature Dry / Wet 20/15℃

 

0.2037 s.