Share on (1600366522889):
Universal Regulation Heater Digital Thermostat Temperature Control
| Model | Control output | Analog output | Communi- cation | Input | Accuracy | Code |
| AI518-SC10 | Voltage output | No | No | Series include types of input signal TC input RTD input Standard analog input(0~10V, 4~20mA,0~50mV,0~400Ω) | ±0.5%FS | A0480AI01 |
| AI518-RC10 | Relay output | No | A0480AI01 | |||
| AI518-KC10 | SCR output | No | A0540AI01 | |||
| AI518-DC10 | Current output | Switchable analog | A0600AI01 | |||
| AI518-SC18 | Voltage output | No | RS485 | A0730AI01 | ||
| AI518-RC18 | Relay output | No | A0730AI01 | |||
| AI518-KC18 | SCR output | No | A0790AI01 | |||
| AI518-DC18 | Current output | Switchable analog | A0850AI01 | |||
| Note:4-20mA output can be as analog output or PID control output in the menu.The factory default is PID control output. | ||||||
| Display | Digits | 4 digits |
| Max | Refer input signal table | |
| Input signal | Input type | TC,RTD universal input Standard analog input,Refer input signal specification table |
| Accuracy | 0.5%FS | |
| Resolution | Display± 0.1℃ | |
| Sampling rate | 2.5 times/second | |
| Analog output | Output points | 1 loop |
| Type | 4~20mA | |
| Range & load | Load resistance 600Ωmax | |
| Output accuracy | 0.5%FS | |
| Resolution | 0.01mA 12 digits | |
| Auxiliary voltage output | Voltage supply | DC 24V |
| Capacity | 30mA max | |
| Relay output | Load | 3A/250V AC |
| Electrical | 10W times | |
| Mechanical | 100W times | |
| Communicaiton | Communicaiton protocol | RS-485 ModBUS-RTU |
| Baud | 4800bps,9600bps | |
| IP range | 1-247 | |
| Delay | No | |
| Power supply | Voltage | 100~240V AC/DC 50/60Hz |
| Power consumption | ≤5W | |
| Protection level | Panel | IP54 |
| Body | - | |
| Environment | Working environment | 0~50℃ <85%RH |
| Storange environment | -20~60℃ <85%RH | |
| Structure | Vibration,pile | 10~55Hz X\\Y\\Z 0.75mm |
| Screw torque | 0.74n.m~0.9n.m | |
| Safe | Dielectric strength | 2000V AC 50/60Hz 1 minute |
| Insulation impedance | 100MΩ DC 500V | |
| EMC | ESD | 3 level |
| Pulse train anti-interference | 4level each mode±4000VP-P | |
| Lightning surge | 3 level N-L ±2000V | |
| Frequency drop | 3 level |




FAQ
Q1.Can you produce according to the samples or drawings?
Yes, we can produce by your samples or technical drawings. We can build the molds and fixtures.
Q2.What is your terms of payment?
Usually,we accept T/T, irrevocable L/C at sight. For regular orders, Terms of payment 30% deposit, full payment before delivery the goods.
Q3.What is the lead time?
For standard models, lead time is about 3~5 days after order confirmed and payment received.
For OEM orders, the delivery is about 2~3 weeks after data confirmed and payment received.
Q4.What is your terms of packing?
Under TOKY brand, the standard packing is 1pc item in a colour box or brown inner box, then into standard export carton.
For OEM order, usually 1pc item in a brown inner box, then into standard export carton.
Q5.What is your terms of delivery?
We accept EXW,FOB,CIF,etc. You can choose the one which is the most convenient or cost effective for you.
Q6.How to solve the quality problems after sales?
Take photos or videos of the problems and send to us.
We will make a satisfied solution for you within 24 hours after we confirm the problems.
Q7.Do you have any MOQ limit for the order?
Low MOQ, 1pc for sample checking is available.
Q8.Is it OK to print my logo on the product?
Yes, OEM service is available.
Please confirm with our sales team formally before production and confirm the design firstly based on our sample.
Q9.Are you manufacturer or trading company?
We are manufacturer for over 30 years. Welcome to visit our factory at anytime.