Environmental Operating Conditions | Fuel Consumption | ||||||
Installation place | Outdoors or indoors (well ventilated) | 100% load with fan (L/h) | 592.2 (ESP) | --- (PRP) | |||
Ambient temperature | -25℃~45℃ (Coolant heater is required when <5℃) | 75% load with fan (L/h) | 444.1 (ESP) | --- (PRP) | |||
Humidity | Less than 80% | 50% load with fan (L/h) | 308.4 (ESP) | --- (PRP) | |||
Altitude | <1000 meters | 25% load with fan (L/h) | 173.5 (ESP) | --- (PRP) | |||
Engine Data | Generator Data | ||||||
Manufacturer | MTU | Manufacturer | Marathon | ||||
Model | 20V4000G63 | Model | MXL-2400-4 | ||||
Output power (ESP/PRP) | 2670 KW | Voltage control | Electronic, self- regulating, +/- 1% | ||||
Number of cylinders / Cylinder configuration | 20/V | Short circuit capability | 3 * nominal current/10s | ||||
Bore / Stroke–mm | 170 /210 | Pole | 4 | ||||
Displacement | 95.4L | Radio interference | EN 55011 Class B, Group 1 | ||||
Compression ratio | 16.4:1 | IP class | IP 23 | ||||
Governor type | Electronic | Insulation class | H | ||||
Injection system | Common rail injection system | Temperature rise class | H | ||||
Cooling mode | Water cooling | Generator efficiency @ 100% load | 93.3% | ||||

Note: Please consult for optional supply scope: | ||||||||
>> Automatic transfer switch | >> Synchronization system | |||||||
>> Coolant heater | >> Lubricant oil heater | |||||||
>> Fuel & water separator | >> External day-use fuel tank | |||||||
>> Anti condensation heater | >> Special-purpose silencer | |||||||
>> Other specific requirements | ||||||||