small current transformer split core 200amp

Share on (1600464740527):


Price:

Quantity:


Product Overview

Description



Product Description






The KCT range of split core current transformers have been specifically designed to be small CT and easy to open and yet maintain the accuracy required for kwh meters. The benefit of a split core current transformer is that it can be placed into position easily and without disturbing or disconnecting the main cables it is monitoring. The KCT range of current transformers has two insulated terminal covers for connecting the S1 and S2 cables which lock down over the terminal screws fully insulating the connections. This makes it ideal to use Autometers cable hamesses which are colour coded and individually numbered on each conductor ensuring simple and easy connection from the current transformer to the electricity meter.





KCT-24 Display




Features

(1) The structure of the self-locking, safe, easy to install, portable
(2) Wide inner window, allowing clamping of big cables or bus-bars
(3) Wide range of sizes to accommodate all the existing installations
(4) Isolated plastic case recognized according to UL94-V0
(5) Wires plugs, Audio plugs, Power plugs and so on five kinds of plugs


Model
Current Ratio
Class/burden
Rated Voltage
KCT-24
100/5A
3.0/1.5VA
660V
KCT-24
150/5A
3.0/1.5VA
660V
KCT-24
200/5A
3.0/1.5VA
660V
KCT-24
250/5A
1.0/1.5VA
660V
KCT-24
300/5A
1.0/1.5VA
660V
KCT-36
150/5A
3.0/1.5VA
660V
KCT-36
400/5A
1.0/2.5VA
660V
KCT-36
600/5A
1.0/2.5VA
660V


Model
KCT-24 Specification
Current Ratio
100A/40mA
200A/40mA
200A/66.7mA
400A/80mA
100-400A/0.333V
Primary Current (A)
100A
200A
200A
400A
100A-400A
Max. Current (A)
150A
240A
240A
480A
480A
Output
40mA
40mA
66.7mA
80mA
0.333V
Load Resistance (Ω)
50Ω
50Ω
50Ω
50Ω
/
Turns Ration
2500:1
5000:1
3000:1
5000:1
/
Class
0.5/1.0
Protection Level
7.5V0-P
Insulation Category
CATIII
Operating Condition
 -20℃ ~ +50℃, ≤85%RH, No condensation, IN-house & Any direction installable
Storage Condition
-30℃ ~ +50℃, ≤85%RH, No condensation


Note: The Current Ratio above are common type, that's ok to customise the ratios according to customers' requirement. 


KCT Application

(1) Current measurement, monitoring and protection for electrical wiring and equipment.
(2) Current and power measurement for electric motors, lighting, air compressor, heating
and ventilation system, air-condition equipment and automation – control system.
(3) Current, power and energy monitoring device.
(4) Relay protection device.


Electrical Parameter
Mechanical Parameter
Frequency
50-2KHz
Case
PA/UL94-V0
Rated Input
5A-600A
Bobbin
PBT
Measuring range
10%In-120%In
Core
Silicon steel
Rated Output
0.333V(AC)or 0-500mA
Internal structure
Epoxy
Ratio
≤ ± 1.0%
Construction
Tie
Phase angle
≤ ±60min
Operation Temp
-25oC~+75oC
Dielectric strangth
2.5KV/1mA/1min
Operating Humidity
≤85%
Insulation Resistance
DC500V/100MΩ min
Output Connection
UL1015 20AWG Wire2.5m




Rated Products






ANA Company








Packing & Delivery






0.0866 s.