Share on (1600539041929):
Model | Control output | Alarm | Analog output 4~20mA | RS485 | Code |
TP-DC18 | 4~20mA | 2 | Multiplex with control output | Yes | B0510TP01 |
TP-DC10 | 4~20mA | 2 | Multiplex with control output | No | B0390TP01 |
TP-MC10 | Relay or SSR | 2 | No | No | B0310TP01 |
TP-RC18 | Relay | 2 | No | Yes | B0430TP01 |
TP-SC18 | SSR | 2 | No | Yes | B0430TP01 |
Sampling speed | 2 times per second |
Relay capacity | AC 250V /3A Life of rated load>100000 times |
Power supply | AC/DC 100 ~ 240V(85-265V) |
Total consumption | < 6VA |
Ambient environment | Indoor use, temperature: 0 ~ 50℃, no condensation,humidity:<85%RH, altitude<2000m |
Storage environment | -10 ~ 60℃, no condensation |
SSR output | DC 24V impulse level, load<30mA |
Current output | DC 4 ~ 20mA load<500Ω,temperature drift 250PPM |
Communication port | RS485 port Modbus-RTU protocol, maximum input:30units |
Insulation impedance | Input, output, power to housing>20MΩ |
ESD | IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B |
Pulse traip anti-interference | IEC/EN61000-4-4 ±2KV perf.Criteria B |
Surge immunity | IEC/EN61000-4-5 ±2KV perf.Criteria B |
Voltage drop & short interruption immunity | IEC/EN61000-4-29 0% ~ 70% perf.Criteria B |
Dielectric strength | Signal input&output & power 1500VAC 1min<60V Low voltage circuit between DC500V,1min |
Weight | About 400g |
Shell material | PC/ABS (flame class UL94V-0) |
Panel material | PC |
Power-off protection | 10 years,times of writing:1 million times |
Safe standard | IEC61010-1 Overvoltage category Ⅱ, pollution level 2, level Ⅱ(Enhanced insulation) |



New products from manufacturers at wholesale prices