NDR-75 75W Rail Type Switching Power Supply | ||||||||
Project | Technical index | |||||||
Output | DC voltage | 12V | 24V | |||||
Rated current | 6.3A | 3.2A | ||||||
Rated power | 75.6W | 76.8W | ||||||
Ripple and noise ① | <120mV | <120mV | ||||||
Voltage accuracy | ±2% | ±1% | ||||||
Output voltage regulation range | ±10% | |||||||
Load adjustment rate | ±1% | |||||||
Linear adjustment rate | ±0.5% | |||||||
Input | Voltage range | 90-264VAC 47Hz~63Hz (127VDC~370VDC:By connecting AC/L(+),AC/N(-) can realize DC input) | ||||||
Efficiency (typical) ② | >85% | >87% | ||||||
Working current | <1.45A 110VAC <0.9A 220VAC | |||||||
Impulse current | 110VAC 20A, 220VAC 35A | |||||||
Start, rise, hold time | 500ms、70ms、32ms :110VAC/500ms、70ms、36ms :220VAC | |||||||
Protect | overload protection | 105%-150% type: constant current output + vaao reduced to undervoltage point cut off output reset: power on again | ||||||
overload protection | ≥ 135% type: constant current output + vaao reduced to undervoltage point cut off output reset: power on again | |||||||
Short circuit protection | VODrop to undervoltage point to close output | |||||||
Environmental Science | Working temperature and humidity | -10℃~+60℃;20%~90RH | ||||||
Storage temperature and humidity | -20℃~+85℃;10%~95RH | |||||||
Safety regulations | Withstand voltage | Input output: 3kVac input shell: 1.5kVac output shell: 0.5kvac for 1 minute | ||||||
Leakage current | <1mA/240VAC | |||||||
Isolation resistance | Input output, input shell, output shell: 500VDC / 100M Ω | |||||||
Other | Size | 40*125*113mm | ||||||
Net/Gross Weigth | 707/750g | |||||||