Share on:
Unit Parameter Table | ||||||
Air-cooled Module Unit Parameter Table | ||||||
Unit Type Unit parameters | ZGR-65ⅡAG2 | ZGR-130ⅡAG2 | ||||
Rated Refrigeration (A35/W7℃) | Cooling Capacity(kW) | 65 | 130 | |||
Power(kW) | 20.3 | 40.6 | ||||
EER | 3.20 | 3.20 | ||||
Rated Heating (A7/W45℃) | Heating Capacity(kW) | 70 | 140 | |||
Power(kW) | 20.5 | 41.0 | ||||
COP | 3.41 | 3.41 | ||||
Mains | 380V/3N~/50Hz | |||||
Maximum Operating Current(A) | 58 | 115 | ||||
Cooling Operating Ambient Temperature Range(℃) | 16~49 | |||||
Heating Operating Ambient Temperature Range(℃) | -15~28 | |||||
Cooling Water Temperature(℃) | 5~25 | |||||
Heating Water Temperature(℃) | 30~50 | |||||
Refrigerant | R410A | |||||
Safeguard | Higher-lower voltage protection, antifreeze protection, overload, water flow protection, etc. | |||||
Capacity Adjustment Method | 0~100% | 0~50%~100% | ||||
Throttling Method | Electronic Expansion Valve | |||||
Water Side Heat Exchanger | Shell and Tube Heat Exchanger | |||||
Wind Side Heat Exchanger | High-efficiency Finned Tube Heat Exchanger | |||||
Fan | High Efficiency and Low Noise Axial Flow Fan | |||||
Water System | Chilled Water Flow(m³/h) | 11.2 | 22.4 | |||
Hydraulic Pressure Drop(kpa) | 40 | 75 | ||||
Maximum Working Pressure(Mpa) | 1.0 | |||||
Water Pipe Connection | DN65(Flange) | DN80(Flange) | ||||
Anti-shock Protection Type | Ⅰ | |||||
Waterproof Level | IPX4 | |||||
Dimentions | Length(mm) | 1930 | 2340 | |||
Width(mm) | 941 | 1500 | ||||
Height(mm) | 2135 | 2350 | ||||
Weight(kg) | 590 | 1000 | ||||
Rated refrigeration: outdoor dry/wet bulb temperature is 35°C/24°C; outlet water temperature: 7°C | ||||||
Rated heating: outdoor dry/wet bulb temperature is 7℃/6℃; outlet water temperature is: 45℃ | ||||||
Models, parameters, and performance will be changed due to product improvements. Please refer to the actual product and nameplate for specific parameters; | ||||||
Executive Standard:GB/T 18430.1(2)-2007 GB/T 25127.1(2)-2010 |