17.5KV vacuum circuit breaker VSG 24KV high voltage draw out type VCB with dpc chassis

Share on:


Price:$800.00 - $1,100.00
Price in USD:Details

Quantity:


Product Overview

Description



Products Description


VS1 vacuum circuit breaker with spring mechanism details listed as belows:
1.Ambient temperature: not higher than +40 °C, not less than -40°C
2. Altitude: not exceed 2000m.
3. Relative humidity: daily average of not more than 95%, month average of not more than 90%.
saturated vapor pressure daily average of not more than 2.2 × 103MPa, month average not more than 1.8 × 103MPa.
4. Earthquake intensity: not more than eight.
5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.
Adopt solid insulation structure, use of advanced solid epoxy sealing technology, the first time, the vacuum interrupter. A
leading electrical circuit. insulation and other support to become an integrated combination of solid seal pole. Successfully from
a fundamental solution of the vacuum breaker gas environment, tolerance issues, make it more broad. Integrated solid-pole closure
of the fluent use of a self-ventilation technology, cleverly solved the structure of solid insulation caused by heat dissipation.
Advantages
Simple structure
Adapt ultra low resistance type vacuum interrupter
Adapt optimization and modular spring operating mechanism
Suitable for occasions with frequent operation
Free maintenance and long service life
High reliable performance


Item
Description
Unit
Data
1
Rated voltage
KV
24
2
Max. voltage
KV
24
3
Rated current
A
630/1250/2500
4
Rated short circuit breaking current
KA
20/25/31.5
5
Rated short circuit making current
KA
50/63/80
6
Rated peak withstand current
KA
50/63/80
7
4S Rated withstand current
KA
20/25/31.5
8


Rated insulation level
Power frequency voltage(when losing a circuit)
KV
Dreaker 65
Impulse withstand voltage(when losing a circuit)
Dreaker 125
9
Rated operating sequence
OC-0.3s-CO-180S-CO
10
Mechanical life
Times
20000
11
Rated short circuit current breaking time
Times
274
12
Rated close brake voltage of operating machnie
V
110,220
13
Rated break brake voltage of operating machnie
V
110,220
14
Contact stroke
mm
13±1
15
Exceed range(the compress length of contact sping)
mm
3.5±0.5
16
Different period of three-phase break and close break
ms
≤2
17
The jump time of contact close break
ms
≤2
18
Average break speed
m/s
1.1~1.7
19
Average closing speed
m/s
0.6~1.1
20


Opening time
Ubder max.operating voltage
S
≤0.05
Under min.operating voltage
≤0.08
21
Closing time
s
0.1
22
Resistance of each phase main loop
μΩ
630≤50 1250≤45/ 1600-2500≤40
23
Contacts limit ersion
mm
3


Details Images




More information and more size ,pls inquiry us directly .OEM is available


Other Products




Company Information






Certifications




FAQ


Q: Are you trading company or manufacturer ?
A: We are factory with more than 20 years experience in this field.

Q: Can I get a sample before the bulk order?
A: Yes, we welcome sample order to test and check quality.Mixed samples are
acceptable.

Q: Can we print our logo/ company name on products?
A: Yes, of course, we accept OEM, then need you to provide brand authorization to us

Q:Do you accept product customization?
A:Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation

Q: How long is your delivery time?
A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days.if the goods are not in stock, it is according to quantity

Q:Do your company have a website ?
A:Please check :www.cnyufeng.cn

Q: How to solve the quality problems after sales?
A: Take photos of the quality problems and send to us for our checking and confirming, we will make a satisfied solution for you within 3 days.

Q: What is your terms of payment ?
A: Payment=5000 USD, 30% T/T in advance ,balance before shippment.


Contact us