Share on (1600720252462):

Item No. | DPR-DKFRS-40II/CDLN | ||||||
Input power | 9.1KW | ||||||
Rated heating | 32KW | ||||||
Range of application | About 200 square meters | ||||||
Number of host matches | 10 HP | ||||||
Our Services | 1. We are direct factory, we accept customized production 2. We have professional team to solve all your problem, and produce as your requirements 3. We can supply the certifications requested 4. Fast Delivery 5. After-sale services. | ||||||

Model | DPR-DKFRS-40II/CDLN | ||
Rated voltage/frequency | 380V~50Hz | ||
Nominal Heating Capacity (A-12 ℃, W41 ℃) | 24.3kW | ||
Nominal Heating input power/current | 9.1kW/15.8 | ||
Rated Heating Capacity(A7℃,W45℃) | 36KW | ||
Rated thermal input power/current | 11.4KW/19.4 | ||
Low-temperature Heating Capacity(A-20℃,W41℃) | 21KW | ||
Rated Refrigeration(A35℃,W7℃) | 25KW | ||
Rated Cooling input power/current | 7.9KW/13.5 | ||
Maximum Input Power/Current | 13.1kW/22.5 | ||
Maximum Water Outlet temperature | 60℃ | ||
Circulating Water Flow | 4.3m³/h | ||
Nominal Heating Capacity/low temperature heating/Rated Refrigeration/COP | 2.67/2.1/3.17 | ||
IPLV(H)/IPLV(C) | 2.9/2.9 | ||
Refrigerant/injection quantity | R410a/4500g*2 | ||
High/low-voltage Maximum allowable pressure | 4.2MPa | ||
The maximum work pressure of the heat exchanger | 4.5MPa | ||
Exhaust/inhalation side allows work over pressure | 4.2/2.6MPa | ||
Water side rated work pressure | 0.7MPa | ||
Water side pressure loss | ≤65kPa | ||
Take-over dimensions | DN40 | ||
Outdoor unit noise | ≤61dB(A) | ||
Category of anti -electric shock protection category | I | ||
Waterproof Level | IPX4 | ||
Size | Length | 1500mm | |
Width | 900mm | ||
Height | 1350mm | ||
Environmental temperature range | -25-43℃ | ||












New products from manufacturers at wholesale prices