Share on (1600862363737):
Model | CR1K (S) | CR2K (S) | CR3K (S) | CR6KS | CR10KS | |||||||
Phase | Single-pahse to ground | |||||||||||
Capacity | 1000VA/1000W | 2000VA/2000W | 3000VA/3000W | 6000VA/6000W | 10000VA/10000W | |||||||
Input | ||||||||||||
Rated voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
Voltage Range | 110-300VAC ±3% at 50% load 176-300VAC ±3% at 100% load | |||||||||||
Frequency Range | 40 ~60 Hz(50HZ system)/50 ~70 Hz(60HZ system) | |||||||||||
Power Factor | 100% load≧0.95 | 100% load≧0.97 | 100% load≧0.97 | 100% load≧0.99 | ||||||||
Output | ||||||||||||
Output Voltage | 220VAC±1%(208,220,230,240 adjustable) | |||||||||||
Voltage Range (Batt. Mode) | ± 1% | |||||||||||
Frequency Range | 47~53Hz or 57~63Hz | |||||||||||
Frequency Range (Batt. Mode) | 50 Hz/60 Hz ± 0.25 Hz | |||||||||||
Current Crest Ratio | 3:1 | |||||||||||
Voltage Distortion | ≦ 3% THD (linear load),≦6% THD (nonlinear load) | |||||||||||
Transfer Time | Utility to Battery | 0ms | ||||||||||
INV to Bypass | 4 ms(standard) | |||||||||||
Waveform (Batt. Mode) | Pure Sine Wave | |||||||||||
Efficiency | ||||||||||||
Utility Mode | 95.0% | |||||||||||
Battery Mode | 92.0% | 94.8% | ||||||||||
Battery | ||||||||||||
Standard Model Battery Model | 12V / 9AH | / | ||||||||||
Standard Model Battery Quantity | 2 | 4 | 6 | / | ||||||||
Standard Charging Time | Charge to 90% in 4 hours | / | ||||||||||
Standard Model Charging Current | 1.0A | / | ||||||||||
Standard Model Charging Voltage | 13.65*N( battery quantity)±1% | / | ||||||||||
Long-run Model Battery Model | Depend on requirments | |||||||||||
Long-run Model Battery Quantity | 3 | 6 | 8 | 16-20(adjustable) | ||||||||
Long-run Model Charging Current | Preselect 6A (1~12A adjustable) | |||||||||||
Long-run Model Charging Voltage | 13.65*N( battery quantity)±1% | |||||||||||
Indicators | ||||||||||||
LCD display | Load,Battery capacity,AC mode,Battery Mode,Bypass Mode,Fault indication | |||||||||||
Alarm | ||||||||||||
Batt. Mode | Alarm beeps every four seconds | |||||||||||
Low battery | Alarm beeps every second | |||||||||||
Overload | Alarm beeps every second | |||||||||||
Fault | Alarm beeps continuously | |||||||||||
Working Environment | ||||||||||||
Temperature & Humidity | Relative humidity 20-90% and temperature 0-40(no condensation) | Relative humidity 0-95% and temperature 0-40 (no condensation) | ||||||||||
Acoustic noise | at 1 meter distance | <50dBA | <55dBA | < 58dBA | ||||||||
Management | ||||||||||||
Smart RS-232 | support Windows® 2000/2003/XP/Vista/2008,Windows®2008/7/8, Linux ,MAC | |||||||||||
Dimension | ||||||||||||
Standard Model Dimension(mm) | 310*438*88(2U) | 380*438*88(2U) | 506*438*88(2U) | / | ||||||||
Long Run Model Dimension(mm) | 380*438*88(2U) | 380*438*88(2U) | 380*438*88(2U) | 580*438*133(3U) | ||||||||
New products from manufacturers at wholesale prices