Share on (1600918388116):
Product Name | 3-Phase String Inverters 12 to 20KW | |
Model | RV-BluE-12KT-M1 | |
PV Input | ||
Max. Input Voltage | 1100V | |
Rated Input Voltage | 620V | |
MPPT Operating Voltage Range | 140V~1000V | |
Start-Up Voltage | 250V | |
Max. Operating Input Current | 15A | |
Max. Short-Circuit Current | 20A | |
No.Of MPP Trackers | 2 | |
No.Of Strings Per MPP Tracker | 2 | |
AC Output | ||
Rated Output Power | 12000W | |
Rated Apparent Power | 13200VA | |
Max. Apparent Power | 13200VA | |
Rated AC Voltage | 400V | |
AC Grid Frequency / Range | 50 Hz / 45 Hz to 55 Hz, 60 Hz / 55 Hz to 65 Hz | |
Max. Output Current | 19.2 A | |
Adjustable Power Factor | ~1 (Adjustable from 0.8 Leading to 0.8 Lagging) | |
Grid Connection | 3-Phase | |
Max. Total Harmonic Distortion (THDi) | ≤ 3 % | |
Efficiency | 5000W | |
Max. Efficiency | 98.60% | |
European Efficiency | 98.10% | |
Protection | ||
DC Switch | YES | |
Anti-Islanding Protection | YES | |
DC Reverse Polarity Protection | YES | |
AC Short-Circuit Protection | YES | |
DC Surge Protection | Compatible with TYPE II Protection Class according to EN/IEC 62109-1 | |
DC Surge Protection | Compatible with TYPE II Protection Class according to EN/IEC 62109-1 | |
Output Over-Current Protection | YES | |
String Fault Detection | YES | |
Insulation Detection | YES | |
Gerneral Data | ||
Dimensions (W x H x D) | 380 X 483 X161mm | |
Weight | <17.0 kg | |
Operating Temperature Range | 25 ~ + 60 °C | |
Self-consumption (at night) | <5.5 W | |
Topology | Transformerless | |
Cooling | Natural Convection | |
Ingress Proction | IP66 | |
Climatic Category | Class 4K4H according to IEC 60721-3-4 | |
Relative Humidity | 0~100% | |
Max. Operating Altitude | 4,000 m (13,123 ft.) (Derating above 2000 m) | |
DC Connection | Plug-In Connector | |
AC Connection | Plug-In Connector | |
Mounting Type | Wall-Mount Bracket | |
Display | LCD | |
Communication Interface | RS485 / Wifi / 4G (Optional) | |
(more available on request) | EN/IEC62109-1/2, IEC/EN61000-6-2, IEC/EN61000-6-4, IEC61683, IEC60068, IEC60529, IEC62116, IEC61727,EN50549-1, AS 4777.2, VDE-AR-N-4105, VDE 0126-1-1, CEI0-21, G98/G99, C10/C11, NB/T32004-2018, GB/T19964-2012 | |