This series of vacuum contactor use overall insulation frame structure with high - quality vacuum switch tube , and secondary control is simple and reliable , stable performance, the external installation of the overall insulation cover , beautiful outlook.
Vacuum contactors utilize vacuum bottle encapsulated contacts to suppress the arc. This arc suppression allows the contacts to be much smaller and use less space than air break contacts at higher currents. As the contacts are encapsulated, vacuum contactors are used fairly extensively in dirty applications, such as mining.
Vacuum contactors are only applicable for use in AC systems. The AC arc generated upon opening of the contacts will self-extinguish at the zero-crossing of the current waveform, with the vacuum preventing a re-strike of the arc across the open contacts. Vacuum contactors are therefore very efficient at disrupting the energy of an electric arc and are used when relatively fast switching is required, as the maximum break time is determined by the periodicity of the AC waveform.
| JCZ5 Series AC vacuum contactor | ||||||
| 160/12(7.2)KV | 250/12(7.2)KV | 400/12(7.2)KV | 630/12(7.2)KV | 800/12(7.2)KV | |
| Main circuit rated voltage (KV) | 12(7.2) | 12(7.2) | 12(7.2) | 12(7.2) | 12(7.2) | |
| Main circuit rated current (A) | 160 | 250 | 400 | 630 | 800 | |
| Main circuit making capacity (A/100times) | 1600 | 2500 | 4000 | 6300 | 8000 | |
| Main circuit break-make ability (A/25times) | 1280 | 2000 | 3200 | 5000 | 6000 | |
| Maximum break ability (A/3times) | 3200 | 4000 | 4500 | 6300 | 8000 | |
| Mechanical life (times) | 100 0000 | 100 0000 | 100 0000 | 100 0000 | 100 0000 | |
| Engineering lock life (times) | 10 0000 | 10 0000 | 10 0000 | 10 0000 | 10 0000 | |
| Electricity life AC3(times) | 25 0000 | 25 0000 | 25 0000 | 25 0000 | 25 0000 | |
| Electricity life AC4(times) | 10 0000 | 10 0000 | 10 0000 | 10 0000 | 10 0000 | |
| Power-frequency withstand voltage for main circuit(fracture)(kv) | 42(32) | 42(32) | 42(32) | 42(32) | 42(32) | |
| Phase-phase phase -to current withstand voltage(KV) | 42(32) | 42(32) | 42(32) | 42(32) | 42(32) | |
| Lightning impulse withstand voltage (KV) | 75(60) | 75(60) | 75(60) | 75(60) | 75(60) | |
| Power-frequency withstand voltage for control circuit(kv) | 2 | 2 | 2 | 2 | 2 | |
| Rated operate frequency(times/h) | 300 | 300 | 300 | 300 | 300 | |
Mechanical lock operating frequencies | 120 | 120 | 120 | 120 | 120 | |
| Terminal pressure(N) | >100 | >100 | >100 | >100 | >100 | |
| Clearance betweenopen contacts (mm) | 6(5)±0.5 | 6(5)±0.5 | 6(5)±0.5 | 6(5)±0.5 | 6(5)±0.5 | |
| Over travel (mm) | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 | |
| Main circuit electric resistance( μΩ ) | ≤200 | ≤200 | ≤200 | ≤200 | ≤200 | |
| Total weight(kg) | 30(25.5) | 30(25.5) | 30(25.5) | 30(25.5) | 30(25.5) | |