Basic Electrical Specifications For Three-in-one-out Products | ||||||||
3C10KRS | 3C15KRS | 3C20KRS | ||||||
Rated Output Capacity | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | |||||
AC Input | Input Method | 3-phase-4-wire+protection wire or single phase 3 wire(neutral wire/live wire+protection wire) | ||||||
Rated Voltage | 208/220/230/240Vac | |||||||
Rated Frequency | 50Hz/60HZ | |||||||
Input Voltage Range | Phase Voltage:90~300VAC±5VAC Line Voltage:156~520VAC ±5VAC | |||||||
Input Frequency Range | (40~70)±0.5Hz | |||||||
Input Power Factor | >0.99 | |||||||
Bypass Voltage | 180~265VAC×(1±3%) | |||||||
Battery Input | Battery Pack Voltage | 192V/240V(selectable) | ||||||
Backup Time(Half Load/Full Load) | Long Term Machine:Depends on External Battry | |||||||
Maximum Inplus Current | < Rated Current 150% | |||||||
Battery Charging Time | 5 hours to 90%(standard type)depending on external battery pack capacity(long-lasting type) | |||||||
AC Output | Output Method | Single-phase-2-wire+protection wire) | ||||||
Output Voltage | 208/220/230/240Vac±2%(Inverter Output) | |||||||
Output Frequency | 50/60Hz±0.5%(Fixed Frequency Mode) 50±5Hz/60±6Hz(Phase-locked Mode) | |||||||
Dynamic Voltage Transients | <9% | |||||||
Dynamic Transient Recovery Time | < 100ms | |||||||
Wave Form | Sine Wave THD <2%(Linear Load) Sine Wave THD <7%(Nonlinear Loads) | |||||||
Output Power Factor | 0.9 | |||||||
Overload Capacity | Mains/ Battery(240VDC)105~125% 10 min,126~150% 1 min, >150% 100ms Battery(192VDC)105~125% 1s,>126% 100ms | |||||||
Conversion Time | Mains<-> Battry Mode 0ms | |||||||
Communication and Monitoring Function | RS232,Network monitoring card,selectable Dry node,MODBUS serveillance card | |||||||
Audio Noise | <65dB | |||||||