Share on (1601006822237):

Model | HYCP8-UF25□ | HYCP8-UIF25□ | HYCP8-UF63□ | HYCP8-UIF63□ | |||
□:U-Upper IN, down OUT □:D-Down IN, upper OUT | |||||||
Functions | Over/under voltage Over/under frequency | Over/under voltage Over/under frequency Overcurrent | Over/under voltage Over/under frequency | Over/under voltage Over/under frequency Overcurrent | |||
Current range | 0.1-25.0A | 0.1-63.0A | |||||
Setting step size 0.1A (maximum display instantaneous current 100A) | |||||||
Voltage range | 60-300V setting step 1V (maximum display voltage 450V) | ||||||
Frequency range | 40-68Hz setting step 1Hz | ||||||
human-computer interaction | Digital display + indicator light + button | ||||||
Detection accuracy | ≤1% | ||||||
Mechanical life | 1x106OPS | ||||||
Environment | Working temperature: -10-55℃ Relative humidity: ≤85% Altitude: ≤2000 meters Storage temperature: -20-75℃, no rain, snow, salt spray and corrosive gas | ||||||
Protection level | IP20 | ||||||
Installation method | 35mm DIN rail type | ||||||
Downtime | 0.1-30.0s | ||||||
Recovery Time | 3-300s | ||||||
Power-on delay | 3-30s | ||||||
Hysteresis value | 1-20% | ||||||
Display brightness | Ld0-3 | ||||||