Share on (1601033942570):
Category | Item | Technical Parameters |
BES | Container Specifications | 20FT |
Full Capacity | 2MWh | |
Adaptable Voltage Range | 500〜1500Vdc | |
Charge and Amplification Rate | O.5CP(1MW PCS Built-in)/lCP(2MW PCS External) | |
Cell Parameters | LFP-3.2V-280Ah-896Wh | |
Module Parameters | LFP-51.2V-280Ah-14.33kWh | |
Cycle Life | 6000 Times-0.5C (90%DOD,≥ 80EOL) | |
Cycle Efficiency | ≥ 94%-0.5C/ ≥ 91%-lC (DC Side) | |
AC Power | Fully Equipped with PCS Power | 1MW |
Basic Parameters | BMS Program | Active balancing + three-level architecture |
Basic Parameters | Communication Interface | Ethernet/RS485/CAN |
Communications Protocol | Modbus-TCP/IEC61850/104 | |
Temperature Control Scheme | lCP-liquid cooled/0.5CP-inverter air-cooled | |
Fire Protection Scheme | Gas, smoke, temperature detection + Novecl230/ FK-5112 + frequency conversion exhaust | |
Insulation Resistance | >10MQ | |
Auxiliary Power Supply | AC380V-50HZ | |
Elevation | ≤ 2000m | |
Permissible Ambient Temperature | -40〜+55°C | |
Permissible Relative Humidity | 0-95RH (No cold dew) | |
Degree of Protection | IP65 | |
Anti-Corrosion Rating | C4 (C5 Optional) | |
Size(L*W*H) | 5800*2300*2400 mm | |
Full Weight | 25T | |
Product Certification | IEC62619 UN38.3 G99 ETL listed conforming to UL1741 / FCC / IEEE1547 / CSA 22.2 CPUC RULE 21 / HECO RULE 14 |