Share on (1601042267973):
Technical specifications | 1000VA | 1500VA | 2200VA | 3000VA | ||||||
Rating (VA/W) | 1000VA/1000W | 1500VA/1500W | 2200VA/2200W | 3000VA/3000W | ||||||
Format | RT2U (tower/rack 2U) | RT2U (tower/rack 2U)and RT3U(tower/rack 3U) | ||||||||
Technology | On-line double conversion with Power Factor Correction (PFC)system | |||||||||
Nominal voltage | 200/208/220/230/240V | |||||||||
Input voltage range | 176-276V without derating (up to 100-276V with derating) | |||||||||
Input frequency rangf | 40-70Hz,50/60Hz autoselection,frequency converter mode | up to 93.5%in online mode | up to 94%in online mode | |||||||
Efficiency | up to 91.5%in online mode up to 92.5%in online mode (up to 97.5%in Hi-efficiency (up to 97.5%in Hi-efficiency | (up to 98%in Hi-efficiency | (up to 98%in Hi-efficiency | |||||||
mode) | mode) | mode) | mode) | |||||||
Connections | ||||||||||
nput | 1 IEC C14(10A) | 1 IEC C20(16A)or terminal block on HotSwap MBP HW (Hard-Wired) | ||||||||
Outputs | 8 IEC C13(10A)sockets | 8IEC C13(10A)sockets +2 IEC C19(16A)sockets | ||||||||
Outputs on HotSwap models | 4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version) | |||||||||
Switched outlet group | 2 outlet groups | |||||||||
Batteries | ||||||||||
Typical backup times* | 300W | 500W | 800W | 1200W | 1800W | |||||
9PX 1000 | 28 | 16 | 9 | |||||||
9PX 1000+1 EBM/+4 EBM | 134/530 | 79/316 | 47/188 | |||||||
9PX 1500 | 38 | 23 | 13 | |||||||
9PX 1500+1EBM/+4 EBM | 143/536 | 86/319 | 52/192 | 32/120 | ||||||
9PX 2200 | 43 | 25 | 15 | 9 | 5 | |||||
9PX 2200+1 EBM/+4 EBM | 206/818 | 123/491 | 74/297 | 47/189 | 29/118 | |||||
9PX 3000 | 60 | 36 | 22 | 13 | ||||||
9PX 3000+1 EBM/+4 EBM | 221/824 | 135/504 | 83/307 | 52/194 | 33/122 | |||||
Battery management | ABM &temperature compensated charging method (user selectable),automatic battery test,deep discharge protection,automatic recognition of external battery units | |||||||||
Communication | ||||||||||
Communication ports | 1 USB port+1 serial RS232 port+1 mini-terminal block for remote ON/OFF+1 mini-terminal block for remote power off +1 mini-terminal block for output relay | |||||||||
Communication slot | 1 slot for Network-M2 card (included in netpack versions),INDGW-M2 or Relay-MS cards | |||||||||
Operating conditions,standards and approvals | ||||||||||
Operating temeprature | 0 to 40℃ | |||||||||
Typical noise level | 35dB | 40dB | ||||||||
Safety | IEC/EN 62040-1,UL 1778,CSA 22.2 | |||||||||
Anprovals &markings | CE /CB report (TUV)/cULus/EAC/RCM /KC/Energy Star | |||||||||
Dimensions H xWxD in mm/Weight | 2U version:86.5*440*605/25kg 2U version:86.5*440*605/27.6kg | |||||||||
UPS | 86.5*440*450/17.4kg | 86.5*440*450/18.9kg | 3U version:130*440*485/24.5kg 3U version:130*440*485/27.4kg | |||||||
EBM | 86.5*440*450/29.8kç | 2U version:86.5*440*605/39.2kg 3U version:130*440*485/38.2kg | ||||||||
Customer service and support | ||||||||||


New products from manufacturers at wholesale prices