Share on (1601178574150):


Product model | ELTE230K120 | ELT114K60 | ||
Battery System Parameters | ||||
Cell Type | LFP 3.2V/280AH | LFP 3.2V/135Ah | ||
Battery Module | 51.2V 280Ah 14.336kWh | 76.8V 135Ah 10.368kWh | ||
Number of Battery Modules | 16 | 11 | ||
Rated Energy | 229.376kWh | 114.048kWh | ||
Rated Voltage | 819.2V | 844.8V | ||
Voltage Range | 665.6~934.4V | 660.0-963.6V | ||
Charge and Discharge Rate | ≤0.6C | ≤0.6C | ||
DOD | 95% | 95% | ||
Lifetime | >6000 cycles | >6000 cycles | ||
Cooling Method | Liquid cooling | Air cooling | ||
Fire Protection System | Thermal aerosol fire extinguishing systems | Thermal aerosol fire extinguishing systems | ||
PCS Parameters | ||||
Rated Power | 120kW | 60kW | ||
Rated DC Voltage | 800V | 800V | ||
Max.DC Current | 176A | 88A | ||
Rated Grid Voltage | 230/400V 3P+N+PE | 230/400V 3P+N+PE | ||
Rated Frequency | 50Hz | 50Hz | ||
Over-load Capability | 1.1 10min;1.2 1min | 1.1 10min;1.2 1min | ||
Maximum Photovoltaic Input Voltage | 1000V | 1000V | ||
Maximum Photovoltaic Power | 60kW | 60kW | ||
MPPT Operating Voltage Range | 200~850V | 200~850V | ||
MPPT Input Way | 1 | 1 | ||
Maximum Input Current | 200A | 200A | ||
System Parameters | ||||
Communication Interface(EMS) | LAN | LAN | ||
Installation Environment | Indoor/outdoor | Indoor/outdoor | ||
IP Grade | IP54 | IP54 | ||
Operating Humidity Range | 5%RH-95%RH | 5%RH-95%RH | ||
Operating Temperature Range | -20C-55C | -20C-55C | ||
Noise | 65db | 65db | ||
Maximum Working Altitude | 3000m | 3000m | ||
Dimensions(L*W*H) | 1850*1070*2350mm | 1360*2000*1130mm | ||
Weight | 2700Kg | 1350kg | ||