Share on (1601209199317):
Models | 80K | 100K | 110K | |||
Input DC | ||||||
Max. input voltage | 1100 V | |||||
Rated voltage | 600 V | |||||
Start-up voltage | 180 V | |||||
MPPT voltage range | 160-1000 V | |||||
Max. input current | 3*(40 A / 32 A) | 4*(40 A / 32 A) | ||||
Max. short circuit current | 6*50 A | 8*50 A | ||||
MPPT number/Max. input strings number | 6/12 | 8/16 | ||||
Output AC | ||||||
Rated output power | 80 kW | 100 kW | 110 kW | |||
Max. apparent output power | 88 kVA | 110 kVA | 121 kVA | |||
Max. output power | 88 kW | 110 kW | 121 kW | |||
Rated grid voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | |||||
Rated grid frequency | 50 Hz / 60 Hz | |||||
Rated grid output current | 121.6 A / 115.5 A | 152.0 A / 144.3 A | 167.1 A / 158.8 A | |||
Max. output current | 133.7 A | 167.1 A | 183.8 A | |||
Power factor | >0.99 (0.8 leading - 0.8 lagging) | |||||
THDi | <3% | |||||
Efficiency | ||||||
Max. efficiency | 98.5% | |||||
EU efficiency | 98.0% | |||||
General Data | ||||||
Dimensions (W*H*D) | 1065*585*363 mm (with AC switch) | 1183*585*363 mm | ||||
Weight | 79.5 kg | 93 kg | ||||
Operating ambient temperature range | -30 ~ +60°C | |||||
Ingress protection | IP66 | |||||
Grid connection standard | G99, IEC61727, EN50549-1/2 | |||||
Safety/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-2/-4 | |||||
Features | ||||||
DC connection | MC4 connector | |||||
AC connection | OT terminal (max. 240 mm²) | |||||
Display | LCD | |||||
Communication | RS485, Optional: Wi-Fi, GPRS, PLC |
New products from manufacturers at wholesale prices