Share on (1601235569769):


Model | 0030TS | 0050TS | 0100TS | 0150TS | 0250TS | 0500TS | ||||||
DC(battery) | ||||||||||||
Voltage range (V) | 250~850 | 320~850 | 420~850 | 420~850 | 420~850 | 500~850 | ||||||
Max. Current (A) | 137 | 178 | 270 | 405 | 673 | 1,128 | ||||||
AC(on-grid) | ||||||||||||
Max output power(kVA) | 33 | 55 | 110 | 165 | 275 | 550 | ||||||
Rate output power(kW) | 30 | 50 | 100 | 150 | 250 | 500 | ||||||
Rated voltage(V) | 400 | |||||||||||
Voltage range(V) | 320~460 | |||||||||||
Rated current(A) | 43 | 72 | 144 | 216 | 361 | 722 | ||||||
Max. output current(A) | 48 | 80 | 59 | 238 | 397 | 794 | ||||||
Rated frequency (Hz) | 50/60 | |||||||||||
AC connection | 3W+N+PE | |||||||||||
General data | ||||||||||||
Max.efficiency | 96.3% | 96.5% | 97.1% | 97.1% | 97.3% | 97.5% | ||||||
Ingress protection | IP21 | |||||||||||
Noise emission (dB) | <70 | |||||||||||
Cooling | Forced air | |||||||||||
Dimension W*D*H (mm) | 800*800*1,900 | 800*800*1,900 | 800*800*1,900 | 800*800*1,900 | 1,200*800*2,050 | 1,600*1,050*2,050 | ||||||
Net Weight(kg) | 621 | 712 | 936 | 1,057 | 1,582 | 2,665 | ||||||
Transformer ratio | 100/400 | 200/400 | 270/400 | 270/400 | 270/400 | 315/400 | ||||||
Self-consumption (W) | <100 | <208 | ||||||||||
On/ Off grid switching | Automatic | |||||||||||
Display and communication | ||||||||||||
Display | LCD touch-screen | |||||||||||
BMS communication | RS485, CAN | |||||||||||
EMS communication | RS485, TCP/IP | |||||||||||
Certificates | IEC/EN62109-1/-2, IEC/EN 62477-1 , IEC/EN 61000-6-2, IEC/EN 61000-6-4, CGC | |||||||||||







New products from manufacturers at wholesale prices