Share on (1601308524519):
Technical Data | GW5K-ET | GW6.5K-ET | GW8K-ET | GW10K-ET | ||||
Battery Input Data | ||||||||
Battery Type | Li-Ion | |||||||
Nominal Battery Voltage (V) | 500 | |||||||
Battery Voltage Range (V) | 180 ~ 600 | |||||||
Max. Continuous Charging Current (A) | 25 | |||||||
Max. Continuous Discharging Current (A) | 25 | |||||||
Max. Charging Power (W) | 7500 | 8450 | 9600 | 10000 | ||||
Max. Discharging Power (W) | 7500 | 8450 | 9600 | 10000 | ||||
PV String Input Data | ||||||||
Max. Input Power (W) | 7500 | 9700 | 12000 | 15000 | ||||
Max. Input Voltage (V)*1 | 1000 | |||||||
MPPT Operating Voltage Range (V) | 200 ~ 850 | |||||||
Start-up Voltage (V) | 180 | |||||||
Nominal Input Voltage (V) | 620 | |||||||
Max. Input Current per MPPT (A) | 12.5 | |||||||
Max. Short Circuit Current per MPPT (A) | 15.2 | |||||||
Number of MPP Trackers | 2 | |||||||
Number of Strings per MPPT | 1 | |||||||
AC Output Data (On-grid) | ||||||||
Nominal Apparent Power Output to Utility Grid (VA) | 5000 | 6500 | 8000 | 10000 | ||||
Max. Apparent Power Output to Utility Grid (VA)*2*4 | 5500 | 7150 | 8800 | 11000 | ||||
Max. Apparent Power from Utility Grid (VA) | 10000 | 13000 | 15000 | 15000 | ||||
Nominal Output Voltage (V) | 400 / 380, 3L / N / PE | |||||||
Nominal AC Grid Frequency (Hz) | 50 / 60 | |||||||
Max. AC Current Output to Utility Grid (A) | 8.5 | 10.8 | 13.5 | 16.5 | ||||
Max. AC Current From Utility Grid (A) | 15.2 | 19.7 | 22.7 | 22.7 | ||||
Power Factor | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | |||||||
Max. Total Harmonic Distortion | <3% | |||||||
AC Output Data (Back-up) | ||||||||
Back-up Nominal Apparent Power (VA) | 5000 | 6500 | 8000 | 10000 | ||||
Max. Output Apparent Power (VA)*3 | 5000 (10000@60sec) | 6500 (13000@ 60sec) | 8000 (16000@60sec) | 10000 (16500@60sec) | ||||
Max. Output Current (A) | 8.5 | 10.8 | 13.5 | 16.5 | ||||
Nominal Output Voltage (V) | 400 / 380 | |||||||
Nominal Output Frequency (Hz) | 50 / 60 | |||||||
Output THDv (@Linear Load) | <3% | |||||||
Efficiency | ||||||||
Max. Efficiency | 98.00% | 98.20% | ||||||
European Efficiency | 97.20% | 97.50% | ||||||
Max. Battery to AC Efficiency | 97.50% | |||||||
Protection | ||||||||
PV Insulation Resistance Detection | Integrated | |||||||
Residual Current Monitoring | Integrated | |||||||
PV Reverse Polarity Protection | Integrated | |||||||
Anti-islanding Protection | Integrated | |||||||
AC Overcurrent Protection | Integrated | |||||||
AC Short Circuit Protection | Integrated | |||||||
AC Overvoltage Protection | Integrated | |||||||
DC Switch | Integrated | |||||||
DC Surge Protection | Type II | |||||||
AC Surge Protection | Type III | |||||||
Remote Shutdown | Integrated | |||||||
General Data | ||||||||
Operating Temperature Range (°C) | -35 ~ +60 | |||||||
Relative Humidity | 0 ~ 95% | |||||||
Max. Operating Altitude (m) | 4000 | |||||||
Cooling Method | Natural Convection | |||||||
User Interface | LED & APP | |||||||
Communication with BMS*5 | RS485, CAN | |||||||
Communication with Meter | RS485 | |||||||
Communication with Portal | WiFi | |||||||
Weight (kg) | 24 | |||||||
Dimension (W × H × D mm) | 415 × 516 × 180 | |||||||
Topology | Non-isolated | |||||||
Self-consumption at Night (W)*6 | <15 | |||||||
Ingress Protection Rating | IP66 | |||||||
Mounting Method | Wall Mounted |