Share on (60015150127):
Genset Automatic Start Module DSE703
DSE703 Generator control panel

DC Supply: | 8 Volts to 35 Volts DC Continuous. |
Cranking Dropouts: | Able to survive 0 Volts for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 Volts. This is achieved without the need for internal batteries. |
Max. Current: | Operating 50mA |
| Standby 10mA |
Alternator Input Range: | 75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%) |
Alternator Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 75V AC Ph-N) (Crank Disconnect from 15V Ph-N @ 20Hz) |
Overspeed +14% (+24% overshoot) | |
Underspeed –20% | |
Start Output: | 1.2 Amp DC at supply voltage. |
Fuel Output: | 1.2 Amp DC at supply voltage. |
Auxiliary Outputs: | 1.2 Amp DC at supply voltage. |
Dimensions: | 125mm x 165mm x 28 mm |
Charge Fail: | 12 Volts = 8 Volts CF 24 Volts = 16 Volts CF |
Operating Temperature Range: | -30 °C to + 70°C |

New products from manufacturers at wholesale prices