Share on (60300033697):








Feature |
•Measure three phase voltage, three phase current, active power, reactive power, apparent power, power factor and frequency with high-precision. |
•Measure forward and reverse active/reactive energy. |
•Measure and timing read time of use energy. |
•Measure total harmonic distortion (THD) and 2-31times odd harmonic components of three phase voltage and three phase current. |
•Provide LED or LCD display and local data query. |
•Visual menus, buttons easy to operate. |
•Programmable current and voltage transformation ratio. |
•Provide multiloop leakage current monitoring |
•Provide multiloop control nodes for alarm and trip control |
•Support the fire alarm and control to cut off power supply of failure point remotely |
•Support RS-485 communications and Modbus-RTU protocol. |
•Supportdigital input, digital output, analog transmission output and energy pulse output. |
•Easy installation, simple wiring, small quantities. |
•Wide range of AC/DC universal power supply: AC / DC 80V~270V |
•Can complete a variety of communication software network in SCADA and PLC. |
Technical Index | |
Accuracy Measurement | |
current | class 0.5 |
Voltage | class 0.5 |
active power | class 0.5 |
reactive power | class 0.5 |
power factor | class 0.5 |
frequency | ±0. 02Hz |
active Energy | class 0.5/class 0.2 |
reactive Energy | class 1.0/class 2.0 |
Input Measurement | |
Wiring | single-phase,3-phase 3-wire,3-phase 4-wire |
Rated current | AC 1A,AC 5A |
Rated voltage | AC 57.7V,AC 100V,AC 220V,AC 380V |
Overload
| Voltage:Sustained:1.2times;Instantaneous:2times/1s |
Current:Sustained: 1.2 times; Instantaneous: 10 times/ 5s | |
Power consumption | Voltage: <1VA (per phase),Current: <0.4VA (per phase) |
Impedance | Voltage: >300KΩ , Current: <20mΩ |
Frequency | 45~65Hz |
Power supply | |
Working range | AC/DC 80V~270V |
Power consumption | <4VA |
Functional Module | |
Communication interface
| 1 loop RS-485 Communication, MODBUS-RTU protocol |
Baud rate: 2400 ~ 19200bps, Default: 2400bps | |
Switching value input | 4 loops switching value input, dry joint |
Switching value output | 3 loops relay output, capability: AC 250V/5A,DC 30V/5A |
Transmission output | 1 loops analog output: 0/4~20 mA or 0~5/10 V |
Energy pulse output | 2 loops energy pulse output, constant: 8000 |
Environment | |
Operational environment | -10℃~+55℃ |
Storage environment | -25℃~ +70℃ |
Relative humidity | ≤93 %,in the place without corrosive gas |
Height above sea level | ≤2500m |
Safety | |
Insulation resistance | > 100MΩ |
AC withstand voltage | AC 2KV |
Electro Magnetic Compatibility | |
Electro-Static discharge | class 4 |
Electrical Fast Transient pulse train | class 4 |
Electrical surge | class 4 |
Outline Dimension | |
External Dimension( mm ) | 120×120;80×80;96×48;96×96;72×72;48×48;120x60;160x80 |
Cutout Dimension( mm ) | 111×111;76×76;92×45;92×92;68×68;45×45;114x56;152x76 |
Specification Matching | |||||||||
Model Function | Measurement | Extended Function(Optional) | Display | Cutout Dimension(mm) | External Dimension ( mm ) | ||||
| single-phase electric parameters | Switch input | Switch output | Transmission output | Communication interface | LED | LCD |
|
|
ME-D1 | √ | 2 | 2 | 1 | 1 | √ | - | 152X76
| 160x80
|
ME-D1Y | √ | 2 | 2 | 3 | 1 | - | √ |
|
|
ME-D2 | √ | 2 | 2 | 3 | 1 | √ | - | 111X111 | 120×120 |
ME-D2Y | √ | 2 | 2 | 3 | 1 | - | √ |
|
|
ME-D3 | √ | 2 | 2 | 3 | 1 | √ | - | 92X92 | 96×96 |
ME-D3Y | √ | 2 | 2 | 1 | 1 | - | √ |
|
|
ME-D4 | √ | 2 | 2 | 1 | 1 | √ | - | 114X56 | 120x60 |
ME-D4Y | √ | 2 | 2 | 1 | 1 | - | √ |
|
|
ME-D5 | √ | 2 | 2 | 1 | 1 | √ | - | 92X45
| 96×48
|
ME-D5Y | √ | 2 | 2 | 1 | 1 | - | √ |
|
|
ME-D6 | √ | 2 | 2 | 1 | 1 | √ | - | 68X68 | 72×72 |
ME-D6Y | √ | 2 | 2 | 1 | 1 | - | √ |
|
|
ME-D7 | √ | 2 | 2 | 1 | 1 | √ | - | 76×76 | 80×80 |
ME-D7Y | √ | 2 | 2 | 1 | 1 | - | √ |
|
|
ME-D8 | √ | 2 | 2 | 1 | 1 | √ | - | 45×45 | 48×48 |
Model Function | Measurement | Extended Function(Optional) | Display | Cutout Dimension ( mm ) | External Dimension ( mm ) | ||||
3-phase electric parameters | Multi-rate | Harmonic | Fire monitoring | Switch input | Switch output | Transmission output | Communication interface | LED | LCD |
|
| |
ME-3D2 | √ | - | - | - | 4 | 4 | 4 | 2 | √ | - | 111X111 | 120x120 |
ME-3D2Y | √ | - | - | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3FD2Y | √ | √ | - | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3HD2Y | √ | - | √ | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3LD2 | √ | - | - | √ | 4 | - | - | 2 | √ | - |
|
|
ME-3LD2Y | √ | - | - | √ | 4 | - | - | 2 | - | √ |
|
|
ME-3FHD2Y | √ | √ | √ | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3D3 | √ | - | - | - | 4 | 4 | 4 | 2 | √ | - | 92X92
| 96×96
|
ME-3D3Y | √ | - | - | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3FD3Y | √ | √ | - | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3HD3Y | √ | - | √ | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3LD3 | √ | - | - | √ | 4 | - | - | 2 | √ | - |
|
|
ME-3LD3Y | √ | - | - | √ | 4 | - | - | 2 | - | √ |
|
|
ME-3FHD3Y | √ | √ | √ | - | 4 | 4 | 4 | 2 | - | √ |
|
|
ME-3D7 | √ | - | - | - | - | - | - | 1 | √ | - | 76×76
| 80×80
|
ME-3D7Y | √ | - | - | - | - | - | - | 1 | - | √ |
|
|
ME-3D6 | √ | - | - | - | - | - | - | 1 | √ | - | 68X68 | 72×72
|
ME-3D6Y | √ | - | - | - | - | - | - | 1 | - | √ |
|
|
ME-3D8 | √ | - | - | - | - | - | - | 1 | √ | - | 45×45 | 48×48 |
Note: The number of optional extended functions would be the maximum number we can extend in normal conditions. If you have any special request, please contact with our technical department. | ||||||||||||