Share on (60636412870):
Range of Professional telecom enclosure ac unit
This series product can be widely use din enclosed area for climate control,such as wireless communication cabinet,battery cabinet,industry contrl cabinet etc.
Here is 300w air conditioner specification sheet
| Name | outdoor cabinet air conditioner |
| Model | A 003/N/E/A |
| Mounting Method | Semi-embedded mounting |
| Power supply | 230VAC±15% 50HZ/60HZ |
| Cooling Capacity | 300W@L35/L35 |
| Power Consumption | 170W@L35/L35 |
| Cooling Capacity | 190W@L35/L55 |
| Power Consumption | 230W@L35/L55 |
| Internal Airflow | 100M³/h |
| Working temperature range | -40℃~+55℃ |
| Max Noise Level | 60db(A) |
| IP Grade | IP55 |
| Net Weight | 14kg |
| Refrigerant | R134a |
| Dimensions | 550*320*175(mm,H*W*D) |
| CE&Rohs Compliant | YES |
| Surface Treatment | outdoor type poweder coating,standard color RAL7035 |
| Heater | 500W optional |
| Hydrogen Function | Optional |
PRODUCT FEATURE OF Professional telecom enclosure ac unit
1 Remote measuring,remote communication,remote control,which can realize multiple automatic protection and comprehensive self-testing function;
2 Strict process control and international brand parts deployed to ensure high quality and reliable of this product;
3 Unique energy-saving & control technology;
4 Fit for T3 high temperature working condition by using of R134a refrigerant gas;
5 Multiple seIf-protection design & visible monitoring interface,RS422 I RS485
communication port
6 LED display,all the settings can be changed at the field;
10 The heating function is optional;
11 Dry contact alarm output,NO/NC optional;
12 Anti-theft design,without the protection cover
Photos of Professional telecom enclosure ac unit
The front

The back of Professional telecom enclosure ac unit
The wooden box packing for the Professional telecom enclosure ac unit

New products from manufacturers at wholesale prices