Smart X96-5F~J Three Phase Multifunction Modbus Communication High Quality Best Power Analyzer with DI/DO Ethernet

Share on:


Price:
Price in USD:Details

Quantity:


Product Overview

Description


2

 

 X96.jpg

 

 

Product description

 

The multifunction energy analyzer SMART X96 F~J series is a top new-generation intelligent panel meter with built-in interfaces provides RS485 Modbus RTU and Ethernet TCP/IP communication. Digital input and outputs are provided for external signal counting and external device control. 30 type's parameters can be set for alarm. This series is widely used not only in the electricity transmission and power distribution system, but also in the power consumption measurement and analysis in LV/MV Intelligent power grid. The Unit can be used as a gateway for Modbus RTU/TCP.

SMART X96 measures and displays the characteristics of 1p2w, 3p4w and 3p3w supplies, including voltage, frequency, current, power and active and reactive energy, imported or exported, Harmonic, Power factor, Max. Demand etc. Energy is measured in terms of kWh, kVArh and kVAh. Maximum demand current can be measured over preset periods of up to 60minutes. The SMART X96 can be configured to work with a wide range of CTs and Pts, giving the unit a wide range of operation.

 

 CorelDRAW X6 Graphic.jpg

 

Characteristics

Multi-parameter Measurements       

Up to 63rd THD and IHD

RS485 Modbus RTU

Ethernet TCP Gateway

Multi-tariffs

Digital Input/Output
Accuracy Class 0.5s

Bar Graph for Power Indication
Backlit LCD Display for Full Viewing Angles

Push-in Installation and Plug-in Connection

 

Technical Specifications

 

 

Electrical characteristics

Type of measurement

RMS including harmonics on three phase AC system (3P, 3P+N)

Measurement accuracy

Active power

1.0% of range maximum

Reactive power

1.0% of range maximum

Apparent power

1.0% of range maximum

Active Energy

IEC 62053-22 Class 0.5S, IEC 62053-21 Class 1.0

Reactive Energy

1.0% of range maximum to IEC 62053-24

Frequency

0.2% of mid-frequency

Current

0.5% of range maximum

Voltage

0.5% of range maximum

Power Factor

1% of unity (0.01)

 

THD

2% to 63rd harmonic

 

Input & Output

Input-Current

Rated Current

5A

Max Current

9999A (for X96-RC 20000A)

Min Current

0.25A

Starting Current

20mA

Output

Contact Rating current

2-27mA at 27V DC

Contact Rating voltage

5-27V DC

Pulse Width

60 / 100 / 200 ms

Pulse rate of S0 1

0.01 / 0.1 / 1 / 10 / 100 kWh/kVArh

 

Pulsed output of S0 2 (non-configurable)

3200IMP/kWh

 

Communications

Modbus RTU (RS485)

 

Type

2-wire half duplex

 

Baud rate

2400,4800, 9600, 19200, 38400

 

Address

1 to 247

 

Mechanical Characteristics

Weight

340g

IP Degree of Protection

(IEC 60529)

IP51 front display

Dimensions (WxHxD)

96x96X92mm

Panel cut-out

92x92mm

Material of meter case

Self-extinguishing UL 94 V-0

Terminals

Voltage: Shrouded screw-clamp

Environmental Characteristics

Operating Temperature

-25 to 55°C

Storage Temperature

-40 to  70°C

Humidity Rating

<95% RH at 50 °C (non-condensing)

Pollution Degree

2

Altitude

2000m

 

ApplicationPacking & DeliveryAbout-us(1)CertificationFAQ


 


0.0164 s.