uninterruptible power supply system Online UPS

Share on (60767316891):


Price:

Quantity:


Product Overview

Description



Product Details








IDEAL 9300LRB 1-20KVA series is true double conversion Online UPS rack or tower convertible type model. With power factor 0.8 / 0.9, it provides high stability and performance when usage. Standard rack mount design can be installed in rack cabinet of data center to offer full range power protection for crucial networking equipment. Smart microprocessor-controlling system assures precious devices under well protection. Individual PDU(Power Distribution Unit) module is designed for 1-3KVA to simplify the steps before UPS maintenance, supporting interruptible power when UPS maintenance. 4sets max. 6-10KVA UPS systems with same capacity or 2 sets max. 20KVA UPS system with same capacity, are available to be connected in parallel for capacity extension. backup UPS systems



Main Features

* Individual power distribution unit (PDU) for fast and easy maintenance (9300LRB 1-3KVA)
* N+X parallel redundancy for capacity expansion and backup support (9300LRB 6-20KVA) 
backup UPS systems
* Isolation transformer for dual output voltage system 110/ 220VAC (9300LRB 6-20KVA)
* Intelligent Slot (SNMP) and USB management software to monitor UPS status
pure sine wave
* ECO mode High efficiency mode for power saving
* Wide input range for extreme voltage instability
 battery backup UPS systems
* External battery bank to extend back-up time
pure sine wave
* Advanced microprocessor control technology
* True double conversion On Line UPS
* Emergency power-off EPO function 
battery backup system
* Automatic self-testing function
 Online UPS 





DSP control

Advanced microprocessor control technology keeps UPS high performance and reliability, operating effectively to save energy.  Online UPS





PDU(Power distribution unit) Module (9300LRB 1-3KVA)

Patent PDU module can save cost and labor hours on UPS maintenance.  Online UPS pure sine wave





Wide input voltage range

Supporting Wide Input Voltage range can offers stable power supplying even in bad AC environment.  rack mount UPS





Automatic self-testing function

Intelligent self-testing function can inspect battery and UPS status to avoid causing any negligence or loss.  rack mount UPS





Double conversion

UPS system works by converting power from AC to DC and then back to AC. Supplying power with zero transfer time to the battery to ensure uninterrupted back-up power when AC power is abnormal, make it ideal for any sensitive devices.  pure sine wave





Application

Offering well and full range protection such as computer center, accounting center, office and home applications. rack mount UPS



Product Introduction










MODEL
IDEAL-9301LRB
IDEAL-9303LRB
CAPACITY UPS
1KVA/0.8KW
3KVA/2.4KW
INPUT
Voltage
1 Phase 2 Wires + Ground 200/208/220/230/240 Vac
Voltage Range
200/208/220/230/240 Vac : 110-300 Vac
Frequency
50Hz or 60Hz (Auto Sensing)
OUTPUT
Voltage
200/208/220/230/240 Vac
Voltage Regulation
200/208/220/230/240 Vac : +/- 2%
Frequency (Battery Mode)
200/208/220/230/240 Vac : 50Hz or 60Hz +/- 0.2Hz
Waveform
Pure Sinewave
THD
200/208/220/230/240 Vac : < 3% (Linear Load), < 5% (Non-linear Load) 
Crest Ratio
3:1
EFFICIENCY
To AC Mode
200/208/220/230/240 Vac : > 88% at Full Load and Battery Full Charged
To Battery Mode
200/208/220/230/240 Vac : > 85% at Full Load and Battery Full Charged
ECO Mode
200/208/220/230/240 Vac : > 93% at Full Load and Battery Full Charged
BATTERY
Voltage
36VDC 
96VDC 
Type
12V/7AH*3pcs
12V/7AH*8pcs
Recharge Time
5Hrs to 90%
TRANSFER TIME
Line <-> Battery
0ms
Inverter <-> Bypass
<4ms
ECO Mode <-> Inverter
< 10ms
DISPLAY
LCD Display
Input, Output, Load, Battery, Mode/Fault/Warning code, Inverter operating, Bypass operating, Output voltage and frequency and Bypass disable / enable selection information
PHYSICAL
Dimension
480*440*88mm
(480*440*88mm)*2


MODEL
9306LRB-12U
9310LRB-12U
IDEAL-9320LRB-19U
CAPACITY UPS
6KVA / 5.4KW
10KVA/9KW
20KVA / 18KW
INPUT
Phase
1 Phase 2 Wires + Ground
Voltage
208/220/230/240 Vac
Frequency
50Hz or 60Hz (Auto Sensing)
OUTPUT
Phase
1Phase 2Wires + G or 1Phase 3Wires + G (With Isolation Transformer)
Voltage
1Phase 2Wires + G : 208 / 220 / 230 / 240Vac or
1Phase 3Wires + G (With Isolation Transformer) :110 / 220Vac or 115 / 230Vac or 120 / 240Vac
Voltage Regulation
+/- 1% ( +/- 2% with Isolation Transformer )
Frequency (Battery Mode)
50Hz or 60Hz +/- 0.05Hz
Waveform
Pure Sinewave
THD
< 2% (Linear Load) or < 5% (Non-Linear Load)
Crest Ratio
3 : 1
EFFICIENCY
To AC Mode
> 92% at Full Load and Battery Full Charged
To Battery Mode
> 92% at Full Load and 12VDC / Battery
ECO Mode
> 96% at Full Load and Battery Full Charged
BATTERY
Voltage
240VDC
Type
12V/7AH *20pcs
12V/9AH *20pcs
12V/9AH *20pcs * 2sets
Recharge Time
7Hrs to 90%
8Hrs to 90%
8Hrs to 90%
TRANSFER TIME
Line <-> Battery
0ms
Inverter <-> Bypass
0ms
ECO Mode <-> Inverter
< 10ms
DISPLAY
LED
Normal (Green ) , Bypass (Yellow) , Fault (Red) , Battery (Yellow)
LCD
Load Level / Battery Voltage / Battery Mode / AC Mode / Bypass Mode Information
PHYSICAL
Dimension(W*H*D)
440*528*630 MM (12U)
440*528*836 MM


Warranty




Our Company






Our Service Team

We, IDEAL, are dedicating on product development and training professional team, we focus on the global market trend to provide innovative power for customers. IDEAL engineering team has professional background experience and technical knowledge and skill, devoting to integrate global market tendency with new technology to ensure products meet the global customer demand. IDEAL design team help customer design customized product package to establish admirable corporate image for marketing.
We are convinced that establishing long-term relationship of mutual trust and mutual benefit between IDEAL and customers is the motion for us to thrive.
With well-trained and professional team, IDEAL support best service and qualified products to customers globally.





Exhibition




FAQ


Why Choose IDEAL?

1) ODM/OEM experience for more than 20 years.
2) Well-organized manufacturing bases to meet worldwide growing demand.
3) Customized products to meet various applications.
4) Full range of power products
5) High quality products supported by strict quality control system
6) Well-trained workforce and engineer team.
7) Reliable manufacturing supplier on E-commerce online platform





FAQ – UPS & Inverter Series

Q1: Why you should install UPS?
When AC Power is off, UPS will offer emergency back-up power to your electronic devices for data loss protection. Power surges are a threat everywhere. UPS can provide fully power protection for over-voltage, under-voltage and surge to offer smooth and consistent flow of power quality to your appliances.
Q2: What electronic appliances should be protected?
All electronic appliances that need long programming times or have to be always accessible would be better to install with a UPS system. This includes computer, medical equipment, data center, server room, networking system and any important electronic appliances.
However, it is not recommended to connect UPS with laser printer or office multifunction fax/printer because they will draw a high initial inrush current at start-up. A typical UPS cannot deal with such a spike.
Q3: What factors can affect UPS battery life time?
Batteries must be kept at ambient temperature of 25°C (77°F). If battery is operated at higher temperatures, its average life will be shortened. The number and length of battery discharges affect a battery's efficiency to deliver power. The more or deeper discharges, the shorter the battery's life will be.
If a battery is undersized for a load, battery run time and life expectancy will also be shortened.
Therefore, it is recommended to replace the batteries every 3 years after initiating the unit.
Recharge batteries every 3 months is necessary if it is not in use.



0.1885 s.