Heat shrink termination Kit Heat shrinkable cables accessories outdoor 3cores cable joint 11KV

Share on (62126928047):


Price:$1.80

Quantity:


Product Overview

Description



Product Description


11KV Heat shrinkable cables accessories outdoor 3cores Heat shrink termination Kit



8.7-15kV, Heat Shrink ,Cable Terminal Kits

Heat shrinkable power cable accessories are provided with the benefits of light weight,reliable application and easy installation.
Suitable for the long-term service from -55℃ to +105℃.Used for the intermediate and terminal joints of oil-immersion cable and cross-linking cable up to 35kV.
Widely applied in industries of electric,power,petrochemical,metallurgy,railway,port and construction,etc.



Detailed Images


Product name
Test item
Test Method
Test result












10kV Heat-shrinkable outdoor termination
AC withstand for 1MIN under rain 1MIN
Neither breakdown nor flashover shall occur at 45kV for rain
No breakdown and flashover occurred on the combination samples at 45kV for 1min
Qualified
AC withstand for 1MIN under rain 1MIN
Neither breakdown nor flashover shall occur at 45kV for rain
No breakdown and flashover occurred on the combination samples at 45kV for 1min
Qualified

Partial discharge test
The magnitude of the discharge at 13KV shall not exceed 20pC.
The magnitude of the discharge of the combination samples didn't exceed 2pc at 13kV
Qualified
Heating cycles voltage test in air
3 cycles at the conductor temperature of 90 to 95℃

Subjected to 3 cycles in air at the conductor temperature of 90 to 95℃

Partial discharge test
The magnitude of the discharge at 13KV shall not exceed 20pC.
The magnitude of the discharge of the combination samples didn't exceed 4pc at 13kV
Qualified

Impulse voltage withstand test
Neither breakdown nor flashover shall occur at 10 positie and 10 negative impulses of 105kV
No breakdown nor flashover occurred on the combination samples at 10 positive and 10 negative impulses of 105kV
Qualified
DC negative polarity voltage withstand for 15MIN
Neither breakdown nor flashover shall occur at 52kV for 15min
No breakdown and flashover occurred on the combination samples at 52kV for 15min
Qualified

AC withstand test for 4H
Neither breakdown nor flashover shall occur at 35kV for 4H
No breakdown and flashover occurred on the combination samples at 35kV for 4H
Qualified