Closed Circuit Industrial Coolers Cooling Systems of Induction Melting Furnace

Share on (62146277311):


Price:

Quantity:


Product Overview

Description


  closed-circuit industrial coolers Cooling Systems of induction melting furnace

 

Tech Specs:
Standard Features:
Able to Cool Multiple Units
No Condensation Problems When Used with a Diversion Valve
Minimum Corrosion, Scaling and Electrolysis
Internal Water-to-Water Heat Exchanger for Ease of Installation
No Coolant Contamination
Completely Closed-Loop Pressurized Circuit
Water-Cooled Design
Reliable Year-Round Cooling
Abnormal Temperature Protection
Audible and Visible Alarms
Full-Access Water Pumping Modules
Fan Cycling Controls for Reduced Power Usage
Optional Features:
Basin Heaters
Basin Sweeping System
Automatic Water Treatment Systems
Factory Tested:
Critical Components

 

Our factory has many induction melting systems operating around the world, our Water Cooling Systems are proven to be suitable for virtually every climate type and temperature extreme. Each system is customized for your application to ensure optimum efficiency. All our cooling systems are protected for abnormal temperature and pressure with audible and visible alarms.

industrial cooler

 

Cooling and melting Systems can be used together to provide proper, year round equipment operation and supplemental heat during the winter months to reduce heating costs.

industrial cooler (3)

 

Reasons include no condensation problems, no coolant contamination, and minimum corrosion, scaling, and electrolysis. These systems can be configured into a variety of different systems depending on the cooling requirements of the system. In a typical dual-loop system, Power Supply Unit cooling is achieved through a heat exchanger coupled to a furnace cooling tower loop. An industrial tower is often used to cool the furnaces because it provides the greatest cooling power in the least amount of space, as well as expelling the most heat.

industrial cooler (2)

 

Water Systems with Closed-Circuit Industrial Coolers have many advantages and are ideal for cooling in any climate for a wide variety of reasons.

 

Technical Sepcification:

Model

DS-N60T

Cooling capacity

300000 kcal/h

Water Flow

60m3/h

Fans parameter

21500m3/h;1.5kw

Fans Quantity

2 Plant

Pump parameter

44.8m3/h;10m;2.2kw    

Pump quantity

1plant

Main circulation pump parameters

50m3/h;32m;7.5kw

main circulation pumps quantity

2plants, one working one stanby

Water supply container

0.5T  304 Stainless steel expansion tank

Water inlet and outlet diameter

DN:100

Water supply diameter

DN:20

Sewage caliber

DN:40

Working pressure

0.15~0.5Mpa

Empty Weight

1250kg

Working wieght

3850kg

main machien dimensions(mm)

2850×1300×2500

Auxiliary machine dimentsions(mm)

1300×1015×1950

 

 


Contact us:
Mob: +86 18336778759


0.1903 s.