Share on (62234657281):
Property | Requirement | Test method | Typical data |
Longitudinal shrinkage | ≤10% | ASTM D 2671 | ≤5% |
Tensile strength | 10.4 MPa min. | ASTM D 638 | ≥12 MPa |
Elongation at break | 200% min | ASTM D 638 | ≥400% |
Tensile strength after ageing (175℃,168hrs) | 7.28 MPa min. | ASTM D 638 | ≥10.4 MPa |
Elongation after ageing (175℃,168hrs) | 100% min. | ASTM D 638 | ≥300% |
Heat shock(250℃,4hrs) | No crack | ASTM D 2671 | No crack |
Low-temperature flexibility(-55℃,4hrs) | No crack | ASTM D 2671 | No crack |
Dielectric voltage withstand | 2500V,60sec, no breakdown | ASTM D 2671 | No breakdown |
Dielectric strength | 19.7 KV/mm min. | ASTM D 2671 | ≥25 KV/mm |