Share on (62439228077):
FT100 intelligent two-wire temperature transmitter. By connecting the sensor
Input signals such as thermal resistance, thermocouple, etc., and input signals
After linearization, the 4-20 mA standard signal and the HART protocol are output.
Output: 4-20mA two-wire system with HART protocol
Configuration: DIP switch + PC programmable (with software)
Accuracy: ≤0.2% or 0.2K
Stability: ≤0.1 °C / year or 0.05% / year
Lightning protection: ±4000V (≤5 times)
Anti-pulse: ±3000~4000V
Temperature drift: 0.008% FS/1°C
Explosion-proof cast aluminum housing waterproof to IP67
Product safety performance reaches SIL2
Integrated temperature transmitter features: Class A sensor with high precision and low temperature drift.
Transmitter module features:
1. Lightning protection ±4000V
2. Anti-pulse ± 3000-4000V
3. Accuracy 0.1%, stability 0.05% / year
4. Dial-up online modification range: 200-550 °C, no software interface modification required.
5. The temperature sensor can be used for various connection methods.
6. There are two types of temperature sensors:
One is called thermal resistance: output resistance signal (V)
Another type of thermocouple: output current signal (4-20mA)
7. Feel free to change the measurement range during use, range -200-550 °C
8. No need to change the original measurement and software settings!
9. Measuring component platinum wire, A grade accuracy!
10. Dial-code module transmitter, no need to replace the thermal resistance, can be directly installed and used, the range can be changed within the measurement range.
11. Module transmitter accuracy is 0.1% and 0.2%
Graduation | T/C (K, S, B, E, J, T, R, N)...... | Display | Back light LCD display can be rotated at any angle. |
Display function | 3 rows digit display & 0 ~ 100% bar chart | ||
RTD | Display unit | °C / °F / °R / °K | |
PT1000 / PT100 / Cu50 / Cu100 | Setting method | Dial code,PC programming | |
Resistance | 0 ~ 600Ω/ 0 ~ 5000Ω | Current output | 4 ~ 20 mA 2 line |
Accuracy | ±0.2%(Range) | MAX Load | (V power-9V) /0.025A |
Stability | Is +/- 0.1% of the range every two years | power supply | 9 ~ 36 VDC |
Temperature influence | Every 10 ℃ for the range of + / - 0.1% | Communication | HART protocol |
CJC compensate | +/- 0.5℃ | Entry hole | |
Analog output | 4 ~ 20 mA | Response time | 1 s |
Liquid material | SUS304 /SUS 316 /SUS 316L / HC / Ta / 316+PTFE |
| |
Shell material | Cast aluminum | ||
Nameplate | SUS 304 | Zero point calibration | Zero calibration can be practiced with the push of a button |
Connection mode | Thread / flange | Quarantine | Input / output / GND isolation up to 480VDC |
Ambient temperature | -40 ~ 85°C | Supply power impact | +/- 0.005 range per V |
Protection level | IP67 (standard) | ||
Humidity limit | 0 to 100% RH | Explosion-proof grade | Isolated explosion-proof Ex D IIB T5 |
Ambient temperature | -25 ~ +85°C | ||
Vibration influence | The frequency is 200 Hz in any direction, +/- 0.05% upper limit per g | Sensor connection | M20*1.5 / M27*2 (inner teeth) |