FGDR32/50 Aluminium Pressure Regulator With Built in Filter Italy giuliani anello Made

Share on:


Price:
Price in USD:Details

Quantity:


Product Overview

Description


 
Product Description

 

Aluminium Pressure Regulator With Built-in Filter

 

Aluminium pressure regulator with built-in filter, to EN 88-1.
Max. inlet pressure 500 mbar. Max. outlet pressure 350 mbar.
Closure control. Suitable for manufactured gas, natural gas, liquefied petroleum gas (LPG), non-aggressive gas and air. Operating temperature range: -15 to +60°C.

 

TECHNICAL SPECIFICATIONS

Inlet pressure range P1:
FGD: +5mbar up to 200mbar

FGDR: +30mbar up to 500mbar

FG1B: +30mbar up to 1bar

Operating Range P2 : neutral spring standard supply; other ranges according to the spring table.

Standard Reference :
FGD- FGDR: EN 88-1
FG1B     : EN 88-2
Governor Class :
FGD – FGDR
:class A
FG1B
:class AC10
Closing Pressure :
FGD
:this model doesn‘t feature test closing
FGDR
:in according with Standard EN 88-1
FG1B
:class  SG30

Resistance: according to EN13611 specifications.

Fuel : Gases of three families: manufactured gas (town gas);natural gas (group H - methane); liquefied petroleum gas(LPG); non-aggressive gas.
Ambient Temperature Range: -15
to +60

Operation : by tensioning the spring, without auxiliary energy.

Construction Features: compensation of inlet pressure,standard supply safety diaphragm, internal pipe impulse. Fast-seal gasket.
All models are supplied with inlet and outlet pipe tap fittings.
 

Material: Aluminum body ,inner parts in aluminum ,steel, brass and synthetic materials; diaphragm and gaskets in nitrile-butadiene rubber.
TECHNICAL FEATURES
Compensation diaphragm, operating diaphragm and safety diaphragm: an external breather outlet pipe is not necessary as the incorporated safety diaphragm ensures that, in the event of breakage of the operating diaphragm,no gas leakage (over 30 dm3/h) is 

possible inside the room (in compliance with par.3.3.2.  EN88 specifications).

INSTALLATION
Install the governor with the diaphragm positioned horizontally (on horizontal pipes). Be careful to follow always the direction of gas flow indicated by the arrow on the regulator/governor.

Suitable tools must be used for the regulator/governor fitting on the inlet and outlet hubs. Never effect leverage on the sleeve of the upper cover when fitting the  regulator/governor.
For all models with the filter inside, the  regulator/governor is best fitted at a comfortable height from the ground so as to faclitate the filter cleaning (fit always a suitable gas filter upstream the governor/regulator).
Make sure that the pipes are clean and aligned so the regulator/governor is not under stress.
Do not remove the perforated diaphragm breather cap (3) and do not obstruct the hole, otherwise the regulator/governor will not work. Install the governor so avoiding contact with plastered walls.
Make sure that the regulator/governor is suitable to the intended use.

 

 

Model

Part Number

Description

End

FGDR32

009.0223.101

With neutral spring 10-25 mbar

1-1/4"

FGDR32

009.0223.102

With green spring 5-15 mbar

1-1/4"

FGDR32

009.0223.103

With violet spring 20-70 mbar

1-1/4"

FGDR32

009.0223.104

With brown spring 65-130 mbar

1-1/4"

FGDR32

009.0223.106

With white spring 120-250 mbar

1-1/4"

FGDR32

009.0223.107

With black spring 240-350 mbar

1-1/4"

 

FGDR.jpg


62528964512