Сохранить в закладки 11000000734392:
Peak-M Intelligent Addressable Fire Detection and Control Panels can be increased up to 2 Loops. The Peak-M Model supports up to 2 Loops - 480 devices. Panel allows the user to see the warnings such as fire / fault; It provides clear and readable text with 4 lines, 40 characters in backlit LCD display. There are 24 built-in zone indicators. The Peak-M model has two conventional sounder outputs with monitoring. USB for computer connection and RS485 / 232 outputs are available as serial port. 1 programmable I / O is available. User Friendly Management Keys and Easy Menu in Turkish. Easy to install and make changes with the configuration software. Ability to display any warning from devices on the panel as desired, with action modes. In factory settings, the basic scenario is assigned as ZONE1 for all inputs and output group for audio and visual devices as 1. When no change is made, if the alarm comes from ZONE1, all audio and visual devices will be active. Loop Distance with 1.5 'cable reaches to 3 Km with 240 devices. (Varies with cable impedance.) Certified with EN54-2 and EN54-4 Standards.
* Complies with Nova Protocol.
* Can be increased from 1 to 2 loops.
* Each Loop supports 240 Devices *
* 1 Fire Relay, 1 Fault Relay and 1 Programmable I / O are available.
* Event memory up to 30,000 (10,000 Alarm, 10,000 Fault, 10,000 Status)
* 4 Lines, 40 Character Backlit LCD Display.
* 24 pcs of Zone Display Panel. * Devices’ Operating Status Reporting Feature.
* Full Configuration Adjustment over the Panel. * Zone / Group, Input and Output Programming + Disabling Feature. Separate Delay Assignment to Outputs is available. * With 1,5’ Cable Loop Distance can be reached to 3 Km with 240 ** devices.
* Used with 2 pieces 12V 7Ah batteries (Batteries are sold seperately from our panels).
* 255 zones, 100 scenarios and 96 output group features (Detectors can also be assigned to the output group. 8 output groups can be assigned in each scenario)
* Loop Card with Isolator
* Night / Day Mode feature
* Test menu, easy setup, automatic Loop and automatic scanning of connected devices, default configuration feature
* Real time Clock / Date * 2 conventional monitored sounder outputs * Optical Smoke Detector
. ** According to cable feature