Домашний Восстанавливающий теплообменник hvac R134a система вентиляции для дома 100 200 м3/ч

Сохранить в закладки 1600167628008:


Цена:40 450,90-155 447,03 ₽*

Количество:

  • В избранное

Описание и отзывы

Характеристики


 



Product Description


 


















































































































































































Hanging type Fresh Air Heat Pump series parameter sheet
 ModelModel number ZJXRA-150ZJXRA-200ZJXRA-300ZJXRA-400
Installation mode Hanging typeHanging typeHanging typeHanging type
 Rated cooling capacityW75083020002300
 Rated heating capacityW80095025002800
 Rated cooling powerW260290550630
 Rated cooling currentA1.231.372.63
 Rated heating powerW260290610685
 Rated heating currentA1.231.372.93.3
 Max operation powerW400430750800
 Max operation currentA1.92.043.63.8
 Compressor/Constant speed compressorConstant speed compressorConstant speed compressorConstant speed compressor
 PowerPower supplyV/Ph/Hz220-240/1/50220-240/1/50220-240/1/50220-240/1/50
 Fresh air/Exhaust air   flowm3/h70~150100~200150~300220~400
 External static pressurePa8080130130
 NoisedB(A)31313132
 Air outlet dimensionmm150150184184
 Condensate drainage sizeinch(BSP)1/2"1/2"1/2"1/2"
 Machine size(L/W/H)mm840/685/250840/685/2501170/760/4001170/760/400
 Packing size(L/W/H)mm891/731/358891/731/3581211/811/4981211/811/498
 Net weight/Gross weightKg43/5043/50120/13595/113
 Refrigerant/R134aR134aR410AR410A

 


Test conditions:


Heating conditions:Ambicnt dry bulb / wet bulb tcmpcraturc7*C/6 < C; Room dry bulb  : wet bulb tcmpcraturc20XT/15*C


Cooling conditions:Ambient dry bulb / wet bulb temperaiure35*C/24X^ ;Room dry bulb / wet bulb temperature27*C/19"C


Fresh Air Heal Pump only handles fresh air.


1. The heating/cooling capacity and heat recovery volume is calculated according to the following conditions:( Remarks: )


Heating: ambient DB=7°C, ambient WB=6°C, indoor DB=20°C   Cooling: ambient DB=35°C, ambient WB=24°C, indoor DB=26°C


2. The airflow is controlled according to the ambient temperature:


Ambient temperature<-15°C, airflow=160m3/h.               -15°C<=ambient temperature<0°C, airflow=320m3/h.


Ambient temperature>=0°C, airflow=480m3/h.


 

Configuration

1. Crossflow heat exchanger: Made of Aluminum, cross flow passages, sensible heat exchanger.


2. Fresh air filters: Triple filtration to ensure air cleanness, G4+F7+H10. Aluminum frame, solid, stable, ametabolic and anti corrosive. 


3. Return air filter: Nonwoven material, G4 class, filtering return air. -Aluminum frame, solid, stable, ametabolic and anti corrosive. 


4. Bypass system: By adjusting the opening angle, different fresh air volume can go through theheat exchanger and by-pass synchronously. When it’s opened completely, the air goes without passing the heat exchanger. 


5. Compressors: Made by Panasonic, rated cooling capacity is 2410W. -R410A refrigeration, environment friendly. 


6. Evaporator: Plate fin heat exchanger, with coated hydrophilic fins. 


7. Connection box: Circuit board, core of intelligent control system -Power switch, power supply to the compressor, fans and by-pass Wiring terminal, easy access for field connection.


8. Electrical heater: 1200W power controlled by the intelligent set program signal.


9. Drain tray: Made of coated galvanized steel, collecting the drain water from heat exchanger, evaporator and condenser. 10. Drain pump -Integrated with ball cock to test the water level, the water is drain out automatically if the water is full.



 

Functions of controller


(1) Operation data display   (2) Airflow adjustment according to ambient temperature    (3) Room temperature setting   (4) Modbus connection    (5) Auto defrosting    (6) Auto bypass  (7) Running mode selection: AUTO-COOLING-HEATING-VENTILATION   (8) Auto restart    (9) Filter monitor   (10) Auto water drain  


(11) Alarm:


A. High pressure or low pressure alarm    B. Communication failure alarm    C. Frosting alarm    D. Short connection or wrong connect of the sensors    E. Sensors fault or short circuit alarm    F. Over heating of electrical heater    G. Fire alarmI. Filter alarm


(12) Multiple protection :


A. High-voltage protection    B. Low-voltage protection    C. Thermal overload protection    D. Over discharge temp. protection of compressor     E. Low supply air temperature protection    F. Drain pump failure protection





Product show


 ZJXRA-400(2)ZJXRA-400(1)ZJXRA-400-2ZJXRA-300.-2


 





Product Overviews


ZJXRA-100~400 14ZJXRA-100~400 15ZJXRA-100~400 16 





Related Products












Company Information


1.jpg 





Certifications


-01 





FAQ


Q1:what’s your ERV machine’s advantage?
A1: overall filtering, adopt multi-filtering screen, the efficiency of filtering rise up to 99%.
 
Q2:can you accept customized needs?
A2: we can do OEM sevice for customers. The specifc needs can be negotiated
 
Q3:Are your machines energy-saving?
A2: yes, our whole series of ERV adopts EC fan motor, less electricity cost,  and safer.
 
Q4: Do your machines have controller board to monitor its operation?
A4: yes, our ERV machines are equipped with our own developing system integrated into its controller board, it’s convenient for customers to ask to find problem accurately and timely.
 
Q5: how do you guarantee your service timely?
A5: both of our engineers and salesmen work at factory office, it can reflect customers’ feedback as soon as possible after shortening the distance between sale department and technical department.
 
Q6: Can your own system be interfaced with other control center by establish communication protocols?
A6: yes, we have many such experiences in this part.


 


 