Сохранить в закладки 1600290401847:
Rated Current(A) | Pole No.(P) | Rated Voltage(V) | Breaking Capacity(A) | Instantaneous Tripping Type | Instantaneous Protective Current Range |
1, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63 | 1, 2, 3, 4 | 230/400 | 6000 | B | 3In |
Release Type | Rated Current Of Release(A) | Initial State | Test Current | Tripping Time | Result | Remarks |
B, C, D | ≤63 | Cold State | 1.13In | t≤1h | Non-tripping | |
Hot State | 1.45In | t<1h | Tripping | The current rise steadily to a fixed value with 5s | ||
≤32 | Cold State | 2.25In | 1s | Tripping | ||
>32 | 1s | |||||
B | ≤63 | Cold State | 3In | t≤0.1s | Non-tripping | |
C | 5In | |||||
D | 10In | |||||
B | ≤63 | Cold State | 5In | t<0.1s | Tripping |