Система сигнализации обнаружения пожарной безопасности Обычная 1/2/4/8/16 система управления сигнализацией
28,00 $
Сохранить в закладки 1600479920191:
item | value |
Brand Name | TNA |
Model Number | TX7004-2 |
No. of Loop : | 2 Loop |
Power Supply: | 240VAC +10%-15%, 50/60Hz |
Certification: | LPCB,CE |
Backup Batteries: | 2 * 12V/24Ah |
PSU Output to CIE : | 24.5 to 28.5 VDC |
Panel to panel communication: | Can Bus [loop] |
Number of Panels: | 512 |
Interface Port: | USB, RS485 Serial, RS232 Serial, Ethernet |
Connectable: | 254 devices/loop (1524 ideal ) |
Memory [Non-Volatile] : | 1000 Fire Events, 10,000 General Event |
Zones: | up to 3000 programmable |
Total Group : | 3,000 programmable |
Sounder Group : | 1,000 programmable |
Common Group: | 2,000 programmable |
Protocol/Addressing : | T&A, Value range from 1 to 254 |
Protection : | Built-in 4Kv Surge protection |
Power rating : | 16 to 24VDC/120mA |
Cabling : | 1.0Km Max Length/2 x 1.5mm²solid core Fire resistance |
Programmable Relays : | 4 circuits, Normally Open/Close |
Programmable Input : | 1 Circuit, Power limited 24Vdc (for future use) |
Programmable Auxiliary Power : | 19 t0 28 VDC (Note: Current Limited) |
Fixed Outputs (FPE/Sounder) : | 2 Circuits, 18 t0 28 VDC (Note: Current Limited) |
Indicator : | 24 LED Status/ 160 Zone Indicators |
Display : | 7” TFT Touch Screen |
Keypad : | 5 Brigade buttons and Programming Keypad |
Relative humidity: | 5 to 95%,non-condensing |
Temperature range: | -5℃~+40℃ |
Packaging Details: | Standard safety export package / carton (Box + Foam) |
Single package size: | 700*660*330mm |
Single gross weight: | 22.14kg |