Сохранить в закладки 1600524657875:
Modes | 3Phase 3wire | 3Phase 4wire | |
Supply terminals | L1,L2,L3 | L1,L2,L3,N | |
Supply voltage | 380V/400V/415V | 220V/230V/240V | |
Operating voltage range | 266V-540V | 154V-312V | |
U> setting value | (105%-125%)×Un | ||
U< setting value | (75%-95%)×Un | ||
Asymmetry setting | adjustable: 5%~20%;fixed:8% | ||
U> trip delay | adjustable: 0.1 ~10s; fixed:2s | ||
U< trip delay | adjustable: 0.1 ~10s; fixed:2s | ||
Asymmetry trip delay | adjustable: 0.1 ~10s; fixed:2s | ||
Hysteresis | 2%fixed | ||
Trip time for incorrect phase sequence and phase failure | <0.5s | ||
Delay error | ±10%+0.1s | ||
Knob setting error | 1% x scale value | ||
Rated insulation voltage | 415V | ||
Output contacts | 1C/0 | ||
Current rating | 8A/250V AC1 | ||
Mechanical life | 106 | ||
Electrical life | 105 | ||
Protection degree | IP20 | ||
Pollution degree | 3 | ||
Altitude | ≤2000m | ||
Operating temperature | -20℃~+55℃ | ||
Permissable relative humidity | ≤50% at 40℃(without condensation) | ||
Storage temperature | -30℃~70℃ | ||
Wire size/Torque | 0.5mm2~2.5mm2 /0.5Nm | ||
Mounting | TH-35 Rail(EN60715) |
Models | U> | U< | Phase failure | Phase sequence | Asymmetry |
RS-MV31(N) | ● | ● | |||
RS-MV32(N) | ● | ● | ● | ||
RS-MV33(N) | ● | ● | ● | ||
RS-MV34(N) | ● | ● | ● | ||
RS-MV35(N) | ● | ● | ● | ||
RS-MV36(N) | ● | ● | ● | ● | |
RS-MV37(N) | ● | ● | ● | ● | ● |
Models | Supply voltage (Un) | Note |
RS-MV31/208 | 3×208 | 3Phase 3wire |
RS-MV31/220 | 3×220 | 3Phase 3wire |
RS-MV31/240 | 3×240 | 3Phase 3wire |
RS-MV31/380 | 3×380 | 3Phase 3wire |
RS-MV31/400 | 3×400 | 3Phase 3wire |
RS-MV31/415 | 3×415 | 3Phase 3wire |
RS-MV31N/220 | 3×380/220 | 3Phase 4wire |
RS-MV31N/230 | 3×400/230 | 3Phase 4wire |
RS-MV31N/240 | 3×415/240 | 3Phase 4wire |
Новинки товаров от производителей по оптовым ценам