Ecsun ups блок питания система online 5 кВА 6 10 20 крепление для стойки центра обработки данных
30 029,78 ₽ - 31 796,24 ₽
Сохранить в закладки 1600537247857:
MODEL | RM060/10X | RM040/10X | RM030/10X | RM020/10X | |||||||
System Capacity | 60kVA | 40kVA | 30kVA | 20kVA | |||||||
Power Module Capacity | 10kVA/10kW | ||||||||||
Phase | 3 Phase+Neutral+Ground, 380V/400V/415V(line-line) | ||||||||||
Voltage Range | 304~478Vac (line-line),full load ; 228V~304Vac (line-line), load decreases linearly according to the min phase voltage | ||||||||||
Rate Frequency | 50/60Hz(Frequency Range :40Hz~70Hz) | ||||||||||
Input PF | >0.99 | ||||||||||
Input THDi | <4% (100% Linear load ) | ||||||||||
Bypass | Voltage Range | 380/400/415Vac (line-line) (Settable , -40%~+25%) | |||||||||
Rate Frequency | 50/60Hz(Settable, ±1Hz, ±3Hz, ±5Hz) | ||||||||||
Bypass Overload | 125% long term operation ; 130% for 10mins ;150% for 1 min ; >150% for 300ms | ||||||||||
Rate Voltage | 380/400/415Vac (line-line) | ||||||||||
Voltage Regulation | 1% for balance load ; 1.5% for unbalance load | ||||||||||
Rate Frequency | 50/60Hz±0.1% | ||||||||||
Output PF | 1 | ||||||||||
Output THDu | <1% , Linear load ; <5.5%, Non-linear load | ||||||||||
Crest Factor | 3:1 | ||||||||||
Inverter Overload | 110% for 1 hour ; 125% for 10 mins ;150% for 1 min ; >150% for 200 ms | ||||||||||
Voltage | ±240Vdc | ||||||||||
Battery Number | 40pcs (Settable: even number from 32 to 44) | ||||||||||
Charge Power | up to 20% * Output active power | ||||||||||
AC Mode | 95.00% | ||||||||||
ECO Mode | 98.00% | ||||||||||
Battery Mode | 94.50% | ||||||||||
Display | 7.0" color touch screen LCD + LED + keyboard | ||||||||||
IP Class | IP20 | ||||||||||
Interface | RS232,RS485,Programmable Dry Contact | ||||||||||
Option | SNMP Card, Parallel kit , SPD, Power module with battery cold start function | ||||||||||
Temperature | Operation : 0~40 ℃,Storage : -40~70 ℃ | ||||||||||
Relative Humidity | 0~95% Non-condensing | ||||||||||
Altitude | <1000m. Within 1000m to 2000m, 1% power derating for every 100m rise | ||||||||||
Noise (1 meter) | 56dB @ 50% load | ||||||||||
Applicable Standards | Safety 安全: IEC/EN 62040-1,EMC : IEC/EN 62040-2,Performance : IEC/EN 62040-3 | ||||||||||
Weight (kg) | Cabinet | 70 | 51 | 55 | 42 | ||||||
Power module | 15.3 | ||||||||||
Dimension | Cabinet | 485*751* 1033 | 485*697* 575 | 485*751* 575 | 485*697* 398 | ||||||
W*D*H(mm) | Power module | 436*590*85 |