Сохранить в закладки 1600808689934:
Mode | W | H | D | A | B |
HE200-T3-0R7G--HE200-T3-2R2G | 72 | 142 | 112.2 | 130 | 61 |
HE200-T3-3R7G--HE200-T3-5R5G | 85 | 180 | 116 | 167 | 72 |
HE200-T3-7R5G--HE200-T3-011G | 106 | 240 | 153 | 230 | 960 |
HE200-T3-015G--HE200-T3-022G | 151 | 332 | 165.5 | 318 | 137 |
Project | Standard specification | ||
Input | Rated voltage, frequency | 1PH/3PH AC 220V 50/60Hz, 3PH AC380V 50/60Hz | |
Voltage allowable range | 220V 170V~240V; 380V:330V~440V | ||
output | Voltage | 220V: 0~220V, 380V:0V~380V | |
Frequency | 0.1 ~ 400.0Hz | ||
Control method | Space vector, V/F control | ||
Show | Four-digit digital tube display, indicator light display, display set frequency, output frequency, output current, rotation direction, rotation speed, fault, etc. | ||
Control characteristics | Output frequency range | 0.1 〜400.0Hz | |
Frequency setting resolution | Digital setting 0.10Hz, analog setting: 0.1% of the maximum output frequency | ||
Output frequency accuracy | 0.1HZ | ||
V/F Control | The V/F curve can be set arbitrarily to meet the needs of various loads | ||
Torque control | Automatic boost: Torque boost is automatically determined according to load conditions; Manual boost: 0.0~20.0% torque boost can be set | ||
Multi-function input terminal | 4 multi-function input terminals, realize 15-stage speed control, 4-stage acceleration and deceleration switching during program operation, UP/DOWN function, emergency stop and other functions | ||
Multi-function output terminal | There is one multi-function output terminal, which can realize the indication and alarm output of running, zero speed, external abnormality, program running, etc. | ||
Acceleration/Decelerat ion time setting | Acceleration/deceleration time can be set separately from 0 to 999.9s | ||
functions | PID control | Built-in PID control | |
RS485 | Standard RS485 communication function (MODBUS) | ||
Analog 0~10V, 4~20mA, keyboard direct setting, RS485 setting, UP / DOWN setting, etc. Note: AVI terminal can select analog voltage input (0~10V) and analog current by switching switch J2 Input (4~20mA) | |||
multi-speed | 4 multi-function input terminals, can form 15 speed | ||
Automatic voltage regulation | Automatic voltage regulation function can be selected as required | ||
Counter | Built-in 2 sets of counters | ||
Protective function | Overload protection | Constant torque 150%/1 minute, variable torque 120%/1 minute | |
Overvoltage protection | Overvoltage protection can be set | ||
Undervoltage protection | Over protection can be set | ||
Other protection | Short circuit protection, over current protection, parameter locking, etc. | ||
Ambient temperature | -10°C~+40°C (no freezing) | ||
Environment humidity | Below 95%(no condensation) | ||
Altitude | Below 1000m(over 1000m, need to downshift) | ||
Vibration | Below 0.5G | ||
Cooling method | Forced air cooling | ||
Protection class | IP20 | ||
Installation method | Wall-mounted, standard 35MM rail installation |