Line Mode Specifications | ||
Input Voltage Waveform: | Sinusoidal (utility or generator) | |
Nominal Input Voltage: | 230Vac | |
Low Loss Voltage: | 170Vac±7V (UPS);90Vac±7V (Appliances) | |
Low Loss Return Voltage: | 180Vac±7V (UPS);100Vac±7V (Appliances) | |
High Loss Voltage: | 280Vac±7V | |
High Loss Return Voltage: | 270Vac±7V | |
Max AC Input Voltage: | 300Vac | |
Nominal Input Frequency: | 50Hz / 60Hz (Auto detection) | |
Low Loss Frequency: | 40±1Hz | |
Low Loss Return Frequency: | 42±1Hz | |
High Loss Frequency: | 65±1Hz | |
High Loss Return Frequency: | 63±1Hz | |
Output Short Circuit Protection: | Circuit Breaker | |
Efficiency (Line Mode): | >95% ( Rated R load, battery fully charged ) | |
Transfer Time:10ms typical (UPS); | 20ms typical (Appliances) | |
Inverter Mode Specifications | ||
INVERTER MODE: | PS-3KVA-24V-50A | |
Rated Output Power: | 3KVA/2400W | |
Output Voltage Waveform: | Pure Sine Wave | |
Output Voltage Regulation: | 230Vac±5% | |
Output Frequency: | 50Hz | |
Peak Efficiency: | 93% | |
Overload Protection:5s@≥150% load; | 10s@105%~150% load | |
Surge Capacity: | 2* rated power for 5 seconds | |
Nominal DC Input Voltage: | 24Vac | |
Cold Start Voltage: | 23.0Vdc | |
High DC Recovery Voltage: | 32Vdc | |
High DC Cut-off Voltage: | 33Vdc | |
No Load Power Consumption: | <25W | |
PWM Solar Charging Mode | ||
Charging Current: | 50Amp | |
System DC Voltage: | 24Vdc | |
Operating Voltage Range: | 30~32Vdc | |
Max. PV Array Open Circuit Voltage: | 80Vdc | |
DC Voltage Accuracy: | +/-0.3% | |
Charge Mode Specifications | ||
Charging Algorithm: | 3-Step | |
AC Charging Current (Max): | 25Amp (@VI/P=230Vac) | |
Flooded Battery : | 29.2V | |
AGM / Gel Battery: | 28.2V | |
Floating Charging Voltage: | 27Vdc |