Сохранить в закладки 1601247515218:
Listed | LPCB Certification |
Compliance | EN 54-12:2002 |
Fire Detection and Alarm Systems | BS 5839 Part 1:2002 |
Operating Voltage | 20 V to 28 V DC |
Current Parameters | Standby: 23mA Commission: 56mA Alarm: 33mA |
Beam Sensor Sensitivity [via Encoder] | Level 1: 2.6 dB High Sensitivity Level 2: 3.8 dB Medium Sensitivity Level 3: 5.8 dB Low Sensitivity |
Beam Pathway Length [via Encoder] | Span 1: 8 to 20 meters Limited Path Span 2: 20 to 40 meters Short Path Span 3: 40 to 70 meters Normal Path Span 4: 70 to 100 meters Long Path |
Beam Path Angle | ±0.4º Directional |
Alignment Guide | Laser Beam Pointer |
Digital Display Guide | Nixie Tube |
LED Indicator Guide | Red: Fire ; Yellow: Fault ; Green: Alignment |
Reset Time | Less than 2 Second |
Relay Capacity [Fire & Fault] | Normally Open & Close/ 2.0 A; 30 VDC |