Сохранить в закладки 1674976138:
Function & Feature of Digital transducer Power transducer active reactive power transducer Latest 3P3W Active and Reactive Power Transmitter,with fast delivery and favorable price,with excellent working performance
AC Active Power (Watt) & Reactive Power (Var) Transducers measure Power in 1 Phase, 3 Phase 3 Wire and 3 Phase 4 Wire in balanced or unbalanced electrical systems and converts it to an industry standard output signal which is directly proportional to the measured input.
Active / Reactive Power Transducer are used for measuring and converting active power and reactive power of a single/three phase system with balanced or unbalanced load into proportion load independent DC current or voltage. GFUVE is the exclusive manufacturer in the fields of consultation , sales and distribution of power industry products including Active/Reactive Power Transducer .
Adopted SCM technique; excellent stability.
Delivering the direction of measured power accurately.
Applicable for active/reactive power measurement in 3P3W.
The product is customized for multi-quantity-combined transducer of current, voltage, power and all quantity measurement in 3P3W, RS485 port support.
Model Description
FUD-Type-Input-Power Supply-Output | |
Type | P3: 3P3W Active Power Transducer Q3: 3P3W Reactive Power Transducer PQ3: 3P3W Active & Reactive Power Transducer |
AC Input | V1: 100V, V2: 0~220V, V3: 270V, V4: 400V A1: 0~1A, A2: 0~5A. |
Power Supply | P1: AC110V±10%, P2: AC220V±15%, P3: AC110V~330V. |
DC Output | O1: 0~20mA, O2: 0~±20mA, O3: 4~20mA, O4: 4~12~20mA, O5: 0~1V, O6: 0~±1V, O7: 0~5V, O8: 0~±5V, O9: RS485. |
Example 1: FUD-P3-V1-A2-P2-O8 | |
FUD Series 3P3W Active Power Transducer | Input: AC100, ±5A , ±866W |
Power Supply: AC220V±15% | |
Output: DC0~±5V | |
Example 2: FUD-PQ3-V1-A2-P2-O8 | |
Details: FUD Series 3P3W Active and Reactive Power Transducer | Input: AC100V, ±5A , ±866W(var) |
Power Supply: AC220V±15% | |
Output: DC0~±5V | |
Please check the Type, Input range, Output range and Power supply at your order. |
Technical Index
Standard | GB/T 13850-1998, IEC688:1992 |
Accuracy | 0.2%, 0.5% |
Consumption | ≤5VA |
Accutacy drift | Annual Variation < 0.2% |
Insulation Voltage | AC 2kV/min.1mA (Between Input ~ Output / Power) |
Insulation Resistance | ≥20MΩ (DC500V) |
Surge voltage | 5KV (Peak Value), 1.2/50μs |
Response Time | ≤350ms |
Input Range | AC 0~5A ,AC 0~500V(Optional), 50/60Hz |
Absorbed Power | Per phase Voltage:≤0.5VA/100V Per phase Current:<0.1VA/5A |
Overload | Current: 2 times continuous,30 times /1s .Voltage: 2 times continuous |
Load Resistance | Current output: RL≤650Ω Voltage output: RL≥2kΩ |
Working environment | Temperature: -10~50°C RH: 20~90%, Without condensation |
Storage conditions | Temperature: -40~70°C RH: 20~95%, Without condensation |
Installation | 35mm DIN Sliding-way or M4 screws |
Dimension | 110mm×75mm×120mm |