Сохранить в закладки 60425600587:
1,Features
1,Rectifier module adopts active power factor compensation technology, power factor up to 0.99.
2,AC input voltage of normal operating range as wide as 42-58V.
3,Rectifier modules adopts full bridge soft switching technology, efficiency can reach above 92%.
4,Perfect battery management: low voltage load disconnect (LVLD) and low voltage battery disconnect (LVBD) to achieve temperature compensation, automatic float control, automatic voltage regulator, battery capacity calculation, online battery test function.
5,Rectifier module adopts no damage hot insert and pull technology, replacement time less than 1min.
6,Network design, providing a variety of communication interfaces (for example: RS232, dry contact), flexible networking can achieve local and remote monitoring, unattended. Perfect DC and DC side lightning protection design used in multi thunderstorm area.
7,Complete fault protection, fault alarm function.
8,Comprehensive operation and maintenance, and can be mounted against the wall, saving space effectively.
9,Ultra-low radiation. Adopt advanced electromagnetic compatibility design, the rectifier module can meet requirements for conducted and radiated interference of "the communication power equipment electromagnetic compatibility Limits and methods of measurement " ( People's Republic of China telecommunications industry standard YD/T983).
10,Safe and reliable. System design in full compliance with safety standards EN60950 and GB4943.
2, Power System Configuration
Optional configuration | Rectifier module | Module maximum number of optional | Distribution | Monitoring module | Remark |
Configuration | 50A | 1pcs | DC distribution: DC48V input, Load output: DC24V10A | Monitor | Specific index refer to module specification |
3, Power system performance index
Input | |||||
Parameter | Min. | Rated | Max. | Unit | Note |
Rated working voltage range |
| 48 |
| Vdc |
|
Input voltage range | 41 | 48 | 59 | Vdc |
|
Output | |||||
Parameter | Min. | Rated | Max. | Unit | Note |
Output voltage range | 20 | 26.5 | 30 | Vdc |
|
Regulation accuracy |
|
| ±0.1 | % |
|
Load regulation |
|
| ±0.1 | % |
|
Source regulation |
|
| ±0.1 | % |
|
Current sharing regulation |
|
| ±0.5 | % |
|
Ripple ( peak – peak value) |
|
| 200 | mv | Network 20MHz testing. |
4,Mechanical Properties:
SIZE: 482.6mm(W)×305mm(D)×88mm(H)
Новинки товаров от производителей по оптовым ценам