Высокоточный бесплатный образец нанокристаллическая сердцевина тороидальная для трансформатора тока

Сохранить в закладки 60763545004:


Цена:*

Количество:

  • В избранное

Описание и отзывы

Характеристики


 


ICTC


Core - Nanocrystalline Core - Instrument Current Transformer Core


 


Key Properties:


1. Higher permeability for higher measuring accuracy (when compared with silicon steel core)


2. Excellent to replacement of Mu-metal


3. High Bs,  1.2T


4. lower manufacturing costs (when compared with permalloy)


5. Long durability range  -30°C ~ + 180°C


 














































Typical Parameter



 



Saturated Induction Density



Bs = 1.2 T



Material Permeability



µo >8x104 Gs/Oe



crystallization temperature



Tx >510



Vickers Hardness



Hv= 880 kg/mm2



Curie Temperature



Tc >570°C



Density



ρ = 7.2 g/cm3



Electrical Resistivity



r = δ ≥130µΩcm



Thickness



29~35µm



Lamination Factor



0.75~0.82



 


 



























































































Materical



Silicon Steel



Nickel Iron



Ferrite



Amorphous



Nano Crystalline



50Ni



80Ni



Mn-Zn



Cobalt Iron



Fe Iron



Bs (T)



2



1.55



0.74



0.5



0.58



1.65



1.2



HC (Oe)



0.5



0.15



0.03



0.1



0.005



0.03



0.1



Initial Permeability (µo)



1500



6000



>40000



3000



>60000



5000



>100000



Max. Permeability (µm)



2 x 104



6 x 104



2 x 105



6 x 103



1 x 106



5 x 104



1 x 106



Resistivity



50



30



60



106



120



130



80



Curie Temperature (°C)



750



500



500



140



225



400



570



Crystallization



-



-



-



-



530



510



510/570



 


 


Main Application:


Instrument current transformer Core with accuracy class 0.2, 0.2s, Bushing current transformer for Epoxy resin cast, Gas insulated or oil-immersed switch-gears, LV, MV and HV switch-gear, power system, relay protection system, power monitoring devices.


 


ICTC Application


CMC Size Drawing


 


 


Flexible Design:


Toroidal Shape, Rectangular Shape, Oval Shape.


ITTC Shape


 


Packing Method: SS+PCB(Stainless Steel+Plastic); DMC (Plastic), Epoxy Resin Coating, Crepe Paper, PMP, DMP, glass cloth ,etc.


ITTC Covering Type


 


Customised Size as request. Our Common Standard for your first reference as below:


ITTC Parameter (1)'


ITTC Parameter (2)'


ITTC Parameter (3)'


ITTC Parameter


 


OEM


We can design & produce goods based on specifications & drawing, specification needed including:


1. Bare core size, Size finished


2. Current Transformer Turns Ratio


3. Capacity (VA)


4. Accuracy 


 


Our Partner:


Top Supplier for Value customers:


Partner


 


Manufacture:


Workshop


 


Certificates:


Certificated


 


 


Safe Package:


 


Safe Package


 


 


We do our best to reply as quickly as we can. If you don’t get a reply within 24 hours, feel free to email us directly at :sales3@coilcore. Some email clients filter email generated by web sites, such as this contact page. The best way to communicate is still by direct email.


 


Похожие товары

Новые поступления

Новинки товаров от производителей по оптовым ценам