Share on (60660940912):
4/6/8/16 Zone Fire Alarm Panel Conventional Fire Alarm Control Panel
Features:
* Four, Six, Eight, Sixteen Zone Style B (Class B) Initiating Device Circuits (IDCs), All zones accept two-wire smoke detectors and any normally-open contact devices.Two Supervisory Input with DC12V output, ideal to connect security alarm devices.
* Three General Alarm, Trouble and Supervisory, Form A Relay Output.
* One, Two, Four Built-in Sound Output, Style Y (Class B) Notification Appliance (Signal) Circuits (NACs), NACs may be programmed: Silenceable or Non-Silenceable.
* 3.0 amps of total system power. Resettable DC24V & Non-resettable DC24V Output.
* Zone Input Short Circuit can be set to “Alarm” or “ Fault” mode.
* RS485 Communication Port (optional). Automatic/Manual mode can be programmed.
* Disable/Enable control per Zone (IDC) can be programmed.
* Disable/Enable Sound Output(NACs) can be programmed.
Technical Specifications:
* AC POWER: 220VAC, 50 Hz.
* BATTERY: Sealed lead-acid batteries only. Maximum charging circuit: 27.6VDC @ 0.8 amp for normal flat charge. Maximum battery charger capacity: 18AH battery.
* NOTE: Two 10AH batteries can be housed in the cabinet. Larger batteries require a separate battery box.
* Total DC24V system power: 3.0 amps.
* Maximum current per NAC: 1.25 amps.
* Maximum battery charging capability: 18 AH.
* Resettable four-wire smoke detector power output.
* Non-resettable power output.
* Integral Form-A Alarm, Trouble and Supervisory relays, rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive).
1 sets fire alarm control panel
1 x English Manual